Alarm only annunciation of points, Alarm/trouble annunciation of points – Fire-Lite LDM-32F Lamp Drivers User Manual
Page 56
Appendix C: MS-9600
Configuration
56
LDM-32F PN 50055:C 03/20/01
Alarm Only Annunciation of Points
The following table displays an example of setting up an LDM Series to
annunciate the control panel’s SLC Loop #1, Modules M65 to M128 in
Alarm Only mode.
By referring to Table 23 on page 52 it can be determined what address can be
set to annunciate any other group of address points.
Table 28 Alarm Only Setup
Alarm/Trouble Annunciation of Points
The following table displays an example of setting up an LDM Series to
annunciate the control panel’s SLC Loop #1, Modules M65 to M128 in
Alarm/Trouble mode. (See Figure 36 on page 55).
By referring to Table 23 on page 52 it can be determined what address can be
set to annunciate any other group of address points.
Table 29 Alarm/Trouble Setup
LDM Module
Address ‘05’
(SLC Loop #1)
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
M65 to M72
M73 to M80
M81 to M88
M89 to M96
LDM-E32F
M97 to M104
M105 to M112
M113 to M120
M121 to M128
LDM Module
Address ‘05’
(SLC Loop #1)
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
M65 to M68
M69 to M72
M73 to M76
M77 to M80
1st LDM-E32F
M81 to M84
M85 to M88
M89 to M92
M93 to M96
2nd LDM-E32F
M97 to M100
M101 to M104
M105 to M108
M109 to M112
3rd LDM-E32F
M113 to M116
M117 to M120
M121 to M124
M125 to M128