beautypg.com

Control switch operation – Fire-Lite LDM-32F Lamp Drivers User Manual

Page 40

background image

Appendix A: Sensiscan 2000

Control Switch Operation

40

LDM-32F PN 50055:C 03/20/01

Control Switch Operation

Circuit corresponds to a specific I/O module installed in user configured
Sensiscan 2000.

The first 8 control switches of the LDM-32F will correspond to CPU switch
functions as shown below, if “8-Point Shift” is not selected.

With “8-Point Shift” selected, the first 8 control switches move to the 3rd LDM-
E32F and are assigned to Circuits 57 through 64 as shown below.

Note: It is assumed that Sensiscan 2000 systems with “8-Point Shift” selected will be 56
zones/points or less.

Table 10 Switch Control Functions

Switch

Position

LDM-32F

-----

3rd LDM-E32F

1

Acknowledge

Not Used

2

Signal Silence

Not Used

3

System Reset

Not Used

4

Not Used

Not Used

5

NAC #1

Not Used

6

NAC #2

Not Used

7

Municipal Tie

Not Used

8

Alarm Relay

Not Used

9

Not Used

Acknowledge

10

Not Used

Signal Silence

11

Not Used

System Reset

12

Not Used

Not Used

13

Not Used

NAC #1

14

Not Used

NAC #2

15

Not Used

Municipal Tie

16

Not Used

Alarm Relay