Configuration, Alarm only annunciation of zones – Fire-Lite LDM-32F Lamp Drivers User Manual
Page 42
Appendix B: MS-9200
Configuration
42
LDM-32F PN 50055:C 03/20/01
Configuration
The control panel needs to be programmed to either “Points” or “Zones”,
depending on which type of address is to be annunciated.
LDM Address Switches (SW1 & SW2) must be set to address ‘01’, ‘02’, ‘03’
or ‘04’. The CPU will differentiate between the addresses.
• For Zones use address 01 (56 zones).
• For Points use addresses 01, 02, 03 and 04 (198 points).
Note: Do not omit any address when annunciating 198 points or the MS-9200 will indicate
a constant trouble.
Alarm Only Annunciation of Zones
The table below illustrates the configuration of the LDM Series modules to
annunciate the alarm state of all 56 software zones (no zone troubles), and two
NACs, with the first eight points of address ‘01’ dedicated to the MS-9200
system function LEDs (see Figure 29 below).
Table 11 Alarm Only Setup
Alarm Only Annunciation of Zones - With 8-Point Shift
The table below illustrates the configuration of the LDM Series modules to
annunciate the alarm state of all 56 software zones (no zone troubles), and two
NACs, with the last eight points of address ‘01’ dedicated to the MS-9200
system function LEDs (see Figure 29 below).
Table 12 Alarm Only Setup with Shift
Figure 29 System Functions to Output Connectors - 1
LDM Module
Address ‘01’
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
Sys Funct
Z1 to Z8
Z9 to Z16
Z17 to Z24
LDM-E32F
Z25 to Z32
Z33 to Z40
Z41 to Z48
Z49 to Z56
LDM Module
Address ‘01’
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
Z1 to Z8
Z9 to Z16
Z17 to Z24
Z25 to Z32
LDM-E32F
Z33 to Z40
Z41 to Z48
Z49 to Z56
Sys Funct
1
2
3
4
5
6
7
8
J5
25
26
27
28
29
30
31
32
J8
System Alarm
System Alarm
Not Used
Not Used
LD
M3
2F-
J
5J8.cdr