Alarm /trouble annunciation of points, Detectors, Modules – Fire-Lite LDM-32F Lamp Drivers User Manual
Page 47: Configuration appendix b: ms-9200, Modules set address ‘03’ and ‘04” for modules

Configuration
Appendix B: MS-9200
LDM-32F PN 50055:C 03/20/01
47
Alarm /Trouble Annunciation of Points
The table below (also see Figure 30 on page 44) illustrates the configuration
of the LDM Series modules to annunciate the alarm and trouble states for all
99 points (detectors or modules) with the first eight points of address ‘01’
dedicated to the MS-9200 system functions (see Figure 31 on page 44).
Detectors
Set address ‘01’ and ‘02’ for detectors.
Table 19 Alarm/Trouble Setup - Detectors
Modules
Set address ‘03’ and ‘04” for modules
Table 20 Alarm/Trouble Setup - Modules
LDM Module
Address ‘01’
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
System Functions
1 to 4
5 to 8
1st LDM-E32F
9 to 12
13 to 16
17 to 20
21 to 24
2nd LDM-E32F
25 to 28
29 to 32
33 to 36
37 to 40
3rd LDM-E32F
41 to 44
45 to 48
49 to 52
53 to 56
LDM Module
Address ‘02’
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
57 to 60
61 to 64
65 to 68
69 to 72
1st LDM-E32F
73 to 76
77 to 80
81 to 84
85 to 88
2nd LDM-E32F
89 to 92
93 to 96
97 to 99
Not Used
LDM Module
Address ‘03’
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
1 to 4
5 to 8
9 to 12
13 to 16
1st LDM-E32F
17 to 20
21 to 24
25 to 28
29 to 32
2nd LDM-E32F
33 to 36
37 to 40
41 to 44
45 to 48
3rd LDM-E32F
49 to 52
53 to 56
57 to 60
61 to 64
LDM Module
Address ‘04’
LDM Output Connectors
J5
J6
J7
J8
LDM-32F
65 to 68
69 to 72
73 to 76
77 to 80
1st LDM-E32F
81 to 84
85 to 88
89 to 92
93 to 96
2nd LDM-E32F
97 to 99
Not Used
Not Used
Not Used