Configuration, Setting rotary switches, M = module d = detector – Fire-Lite LDM-32F Lamp Drivers User Manual
Page 52

Appendix C: MS-9600
Configuration
52
LDM-32F PN 50055:C 03/20/01
Configuration
Setting Rotary Switches
LDM Address Switches (SW1 & SW2) must be set to an address. Use the
following table to set these switches.
Note: Do not omit any address when annunciating 636 points or the MS-9600 will indicate
a constant trouble.
M = Module D = Detector
Table 23 SW1 & SW2 Switch Settings
Note: If a UDACT-F is installed and selected in control panel programming, it will
automatically assign addresses 20 - 31 to the UDACT-F and disable the selection of
these addresses.
FACP
Address
SW1
SW2
Relay Activation for:
1
0
1
8 System Points & Zones 1-56
2
0
2
Zones 57-99 & 2 NACs
3
0
3
Loop 1, Address M1 - M64
4
0
4
Loop 2, Address M1 - M64
5
0
5
Loop 1, Address M65 - M128
6
0
6
Loop 2, Address M65 - M128
7
0
7
Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159
8
0
8
Loop 1, Address D1 - D64
9
0
9
Loop 2, Address D1 - D64
10
1
0
Loop 1, Address D65 - D128
11
1
1
Loop 2, Address D65 - D128
12
1
2
Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159
13 - 19
Not Used
20
2
0
8 System Points & Zones 1-56
21
2
1
Zones 57-99 & 2 NACs
22
2
2
Loop 1, Address M1 - M64
23
2
3
Loop 2, Address M1 - M64
24
2
4
Loop 1, Address M65 - M128
25
2
5
Loop 2, Address M65 - M128
26
2
6
Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159
27
2
7
Loop 1, Address D1 - D64
28
2
8
Loop 2, Address D1 - D64
29
2
9
Loop 1, Address D65 - D128
30
3
0
Loop 2, Address D65 - D128
31
3
1
Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159