beautypg.com

Edwards Signaling 5536MHV-24 User Manual

Millennium local/system signal, Description and operation, Installation

background image

P/N 3100009 ISSUE 2 © 2003

Installation Instructions for Catalog Series 5536M-24 and

5536MHV-24 Adaptatone

®

Millennium Local/System Signal

Description and Operation

Description and Operation

Description and Operation

Description and Operation

Description and Operation

Edwards Adaptatone is a heavy-duty, tone-selectable, stand

alone, indoor/outdoor audible signaling device intended

for industrial applications where high audible output and

microcomputer reliability are required. Catalog Numbers

ending with suffixes -24AQ or -24Y6 are CE Marked and

TUV-RHEINLAND Certified for compliance to the European

Union's Electromagnetic Compatibility (Industrial) and Low

Voltage Safety Directives (see Declaration of Conformtiy,

available upon request). Additionally, the Adaptatone

Millennium series are UL and cUL Listed as Audible Signal

Appliances for use in the following hazardous locations.

Installation

Installation

Installation

Installation

Installation

The Adaptatone may be mounted to any flat surface or

may be used as a freestanding unit mounted to a rigid

pipe. The Adaptatone must be installed in accordance

with the latest edition of the National Electrical Code or

other regulations applicable to the country and locality

of installation and by a trained and qualified electrician.

NOTE: The increased resistance due to long wire runs

needs to be accounted for in sizing wire.
Consult Applications Engineering for details.

For catalog numbers ending in "AQ", 24V AC power must

be transformer isolated from mains or line power.

1. Mount Adaptatone as shown in Figure 2.

a. Flat Surface Mounting. Secure unit to

mounting surface using the (4) mounting holes in

the mounting plate on the rear of the box. Use

the #10 x 3" (76 mm) wood screws (furnished loose)

or other hardware (not supplied) suitable for the

mounting surface.

b. Rigid Pipe Mounting. Loosen the (4) cover screws

from the signal box and lift off signal box cover.

NOTE: Cover screws are captive. Do not remove from

cover.

Remove the center knockout in lower wall of box

and mount box to a 1/2" (12.7 mm) conduit pipe

using suitable connector.

Dimensions

5536M

5536MHV

A

8 7/8"

11 1/2"

(225 mm)

(292 mm)

B

8 1/4"

9 3/4"

(210 mm)

(248 mm)

C

13"

16 1/2"

(330 mm)

(419 mm)

Figure 1. Dimensions

Input Board

Main Power

Catalog

Current (A)

Number

Voltage

Current

Voltage

Standby

Tone On

Standard Volume

5536M-24AQ

24V DC

6 mA

24V DC

0.10

0.74

24V AC 50/60 Hz

0.10

1.3

5536M-24N5

24V DC

6 mA

120V AC 50/60 Hz

0.10

0.36

5536M-24Y6

24V DC

6 mA

125V DC*

0.10

0.21

250V DC*

0.02

0.10

120V AC 50/60 Hz

0.10

0.32

240V AC 50/60 Hz

0.10

0.20

High Volume

5536MHV-24AQ

24V DC

6 mA

24V DC

0.10

1.5

24V AC 50/60 Hz

0.10

2.3

5536MHV-24Y6

24V DC

6 mA

125V DC*

0.10

0.39

250V DC*

0.02

0.19

120V AC 50/60 Hz

0.10

0.56

240V AC 50/60 Hz

0.10

0.34

*CE mark and T

ÜV-Rheinland Certifications do not apply to 125V DC or 250V DC.

CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH SERV.)

Catalog

Hazardous

Temp.

Number

Locations

Code

5536M-24AQ

Class I, Div. 2, Groups A, B, C, D

T4 (135C)

5536M-24N5

Class II, Div. 2, Groups F, G

T5 (100C)

5536M-24Y6

Class III, Div. 1 and 2

5536MHV-24AQ
5536MHV-24Y6

The Adaptatone operates from local power and sounds a

high decibel signal determined by the setting of minia-

ture programming switches inside the unit. The

Adaptatone may be programmed for any of the 27 tones

listed in Figure 11.
Three tones may be programmed into the unit at any time.

These tones operate on a pyramid-type priority system.

The tone programmed on SW2 overrides the tones pro-

grammed on SW3 and SW4. The tone on SW3 overrides

the tone programmed on SW4. An external audio signal

up to 12V RMS can be connected to take priority over all

internally generated tone signals.
The decibel output level and speaker lateral position are

both easily adjustable.

Mechanical Specifications

Mechanical Specifications

Mechanical Specifications

Mechanical Specifications

Mechanical Specifications

Weight ................................................... 9 Pounds (4.1 kg)
Hazardous Locations, UL Standard UL1604

Ambient Temp. ................... +41F to +104F (+5C to +40C)
Non-Hazardous Locations

Variable Ambient Temp. ..... -40F to +151F (-40C to +66C)

Hazardous Locations and Variable Ambient Conditions apply only
where UL listings are accepted and do not apply to CE conformity or
TUV-Rheinland Certification.

Electrical Specifications

Electrical Specifications

Electrical Specifications

Electrical Specifications

Electrical Specifications

W A R N I N G

W A R N I N G

W A R N I N G

W A R N I N G

W A R N I N G

To prevent fire, shock and component damage, NO work,
including circuit board removal, should be performed while
the circuit is energized.

NOTE: Any kind of service or maintenance performed
while unit is energized will void the warranty.

This manual is related to the following products: