Maintenance, Specifications – Edwards Signaling Integrity Synchronized Temporal Horn-Strobe User Manual
Page 3
P/N 3100376 • REV 6.0 • ISS 06MAY11
3 / 6
Figure 2: Typical one-circuit wiring diagram
(1)
(2)
NAC +
NAC +
NAC –
NAC –
Polarity is shown in the active state.
(1) From UL/ULC Listed fire alarm control panel signal circuit.
(2) To next device or end of line resistor for Class B. Return to control
panel for Class A connection.
Figure 3: Typical two-circuit wiring diagram
(1)
(2)
NAC1 +
NAC1 +
NAC2 +
NAC2 +
NAC1 –
NAC1 –
NAC2 –
NAC2 –
Polarity is shown in the active state.
(1) From UL/ULC Listed fire alarm control panel signal circuit.
(2) To next device or end of line resistor for Class B. Return to control
panel for Class A connection.
Mounting the electrical box
Figure 1 shows mounting details for:
•
Standard box. When using a 4 in. square box, use an
extension ring for additional wiring space, if needed. If
using a double-gang electrical box that is 2-1/2 in.
(64 mm) deep, locate the conduit only at the rear of the
box.
•
Weatherproof box. Peel off the adhesive backing from the
gasket and adhere to the box.
•
Surface mount box.
Selecting the volume and tone
The horn has a jumper for selecting a high or low volume
output level. The default is high volume. To set the output to
low volume, remove the output jumper from the circuit board
on the rear of the unit. See Figure 4 below.
The horn has a jumper for selecting either a temporal or steady
tone. The default is temporal tone. To set the output to steady
tone, remove the tone jumper from the circuit board on the rear
of the unit.
Tip:
Save the jumper by sliding it onto a single pin.
Figure 4: Jumper setup and terminal block
REMOVE FOR
LOW OUTPUT
REMOVE FOR
CONT. TONE
HORN
+
HORN
–
STROBE +
STROBE –
1
2
3
4
(1)
(2)
Item In
Out
(1)
High output
Low output
(2) Temporal
tone
Steady
(continuous)
tone
Maintenance
Note:
Do not change the factory-applied finishes.
This unit is shipped from the factory as an assembled unit; it
contains no user-serviceable parts and should not be
disassembled.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
Specifications
Operating voltage
16 to 33 VDC, 16 to 33 VFWR
Strobe operating current See Table 4
Horn operating current
See Table 5
Sound output
See Table 6 and Table 7
Light output
See Table 10
Horn temporal pattern
0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s
on, 1.5 s off, repeat cycle
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Compatible electrical
boxes
2-1/2 in. (64 mm) deep double-gang,
4 in. square box 2-1/8 in. (54 mm) deep,
Surface or bidirectional mounting box per
Table 2
Operating temperature
Indoor
UL
outdoor
ULC
outdoor
32 to 120°F (0 to 49°C)
−35 to 150°F (−37 to 66°C)
−40 to 150°F (−40 to 66°C)
Relative humidity
Indoor
Outdoor
93% noncondensing
98% noncondensing