beautypg.com

Edwards Signaling Integrity Synchronized Temporal Horn-Strobe User Manual

Description, Installation

background image

© 2011 UTC Fire & Security. All rights reserved.

1 / 6

P/N 3100376 • REV 6.0 • ISS 06MAY11

Description

The Integrity Synchronized Temporal Horn-Strobe is a fire
alarm notification appliance designed for indoor or outdoor
walls and ceilings. (The 15 cd strobe is for indoor use only.)
For model numbers, see Table 1; for accessories see Table 2.

Table 1: Models

Description Numbers

15 cd horn-strobe, red [1]

757-5A-T
XLS757-5A-

INT-5AT
2452THS-15-R

15 cd horn-strobe, white [1]

757-5A-TW
XLS757-5A-TW

INT-5ATW
2452THS-15-W

30 cd horn-strobe, red

757-3A-T
XLS757-3A-T

INT-3AT
2452THS-30-R

30 cd horn-strobe, white

757-3A-TW
XLS757-3A-TW

INT-3ATW
2452THS-30-W

75 cd horn-strobe, red [2]

757-4A-T
XLS757-4A-T

INT-4AT
2452THS-75-R

75 cd horn-strobe, white [2]

757-4A-TW
XLS757-4A-TW

INT-4ATW
2452THS-75-W

15/75 cd horn-strobe, red

757-7A-T
XLS757-7A-T

INT-7AT
2452THS-15/75-R

15/75 cd horn-strobe, white

757-7A-TW
XLS757-7A-TW

INT-7ATW
2452THS-15/75-W

110 cd horn-strobe, red

757-8A-T
XLS757-8A-T

INT-8AT
2452THS-110-R

110 cd horn-strobe, white

757-8A-TW
XLS757-8A-TW

INT-8ATW
2452THS-110-W

[1] For indoor use only
[2] Not ULC Listed

Table 2: Accessories

Description Numbers

Surface box, red, indoor

757A-SB
XLS757A-SB

INT-SB
2459-SMB-R

Surface box, white, indoor

757A-SBW
XLS757A-SBW

INT-SBW
2459-SMB-W

Weatherproof box, red,
outdoor

757A-WB
XLS757A-WB

INT-WB
2459-WPB-R

Weatherproof box, white,
outdoor

757A-WBW
XLS757A-WBW

INT-WBW
2459-WPB-W

Bidirectional mounting frame,
red, indoor

757A-BDF
XLS757A-BDF

INT-BDF
2459-BDF-R

Bidirectional mounting frame,
white, indoor

757A-BDFW
XLS757A-BDFW

INT-BDFW
2459-BDF-W

The strobe operates on any existing two-wire signal circuit.
There are jumpers for selecting either a temporal or steady
tone, and high or low volume. See Figure 4 for the jumper
locations.

The strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling
Devices for the Hearing Impaired
and CAN/ULC-S526 Visible
Signal Devices for Fire Alarm Systems, Including Accessories.
Synchronized operation requires a separately installed
synchronization control module. See Table 3 for a list of
compatible synchronization modules.

Table 3: Compatible synchronized models

Description Numbers

Auto-Sync Output Module

SIGA-CC1S

SIGA-MCC1S

Genesis Signal Master -
Remote Mount

ADTG1M-RM
XLSG1M-RM
G1M-RM
BPS-6(10)A

MG1M-RM
EG1M-RM
ZG1M-RM
APS-6(10)A

Installation

WARNING:

Electrocution hazard. To avoid personal injury or

death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.

Notes

Electrical supervision requires the wire run to be broken at
each terminal. Do not loop the signaling circuit field wires
around the terminals.

To ensure flash synchronization, do not install this
enhanced strobe (identified by a red cd rating on the front
of the unit) in the same field of view as older models
(identified by a black cd rating on the front of the unit).

Install this product in accordance with applicable requirements
in the latest editions of NFPA 72, National Fire Alarm and
Signaling Code,
and CSA C22.1 the Canadian Electrical Code,
Part 1, Section 32, CAN/ULC-S524 Installation of Fire Alarm
Systems
and in accordance with the local authority having
jurisdiction.

Integrity Synchronized Temporal Horn-Strobe

Installation Sheet