Electrical Specifications
Table 2. PLC Compatibility
Catalog Number
Operating
Voltage
Max. off state leak-
age current
Continuous on
current
Surge (inrush/duration)
105XBRiRGA24D
24V DC
5 mA
150 mA
28.5 A / 65 μSeconds
105XBRiRBA24D
105XBRiRGA120A
120V AC 50/60 Hz
5 mA
100 mA
28.5 A / 212 μSeconds
105XBRiRBA120A
To avoid risk of injury, install lens before
energizing the unit and do not remove or
insert light source when unit is energized.
WARNING
1. Select a mounting configuration (Figure 3).
NOTE: When mounting using the Cat. No. 105BM
mounting bracket, the Cat. No. 105BX outlet
box attachment must also be used as shown in
Figure 1.
2. Pull field wiring from conduit into the mounting
attachment.
WARNING
To prevent electrical shock, ensure that power
is turned off before installing the signal.
Catalog Number
Electrical Specs
Red, Green, Amber
105XBRiRGA24D
24V DC, 0.150 A
105XBRiRGA120A
120V AC*, 0.100 A
Red, Blue, Amber
105XBRiRBA24D
24V DC, 0.150 A
105XBRiRBA120A
120V AC*, 0.100 A
* 120V AC 50/60 Hz
Installation
Installation must be in accordance with local codes. The lens
should be positioned up for outdoor applications.
Do not disconnect equipment unless power
has been removed or the area is known to be
non-hazardous.
WARNING - EXPLOSION HAZARD
To prevent electrical shock, do not connect
power until instructed to do so.
WARNING
WARNINGS
The 105BX junction box, 105BM mounting
bracket and 105PM pipe mount attachments
are non-conductive plastic fixtures and do not
provide earth-ground continuity when attached
to metallic wiring systems. Therefore, they
are intended for use with the 105XBRi series
visual signals only when earth-grounding is not
required.
The 105BX junction box, 105MB mounting
bracket and 105PM pipe mount attachments
can be used with metallic wiring systems only
when installed at the end of the run.
3. Install the mounting attachment as follows:
a. Cat. No. 105BX: Secure the outlet box attachment to
the mounting surface using two screws (not supplied)
suitable for the surface. Attach the adhesive backed
gasket to the top of the 105BX mounting box, being
careful to line up the holes in the gasket with the
mounting holes in the outlet box.
b. Cat. No. 105BM: Using the four supplied screws,
secure the mounting bracket to Cat. No. 105BX
outlet box attachment as shown in Figure 1. Attach
the adhesive backed gasket to the top of the 105BM
mounting bracket, being careful to line up the holes
in the gasket with the mounting holes in the outlet
box. Refer to Figure 1.
c. Cat. No. 105PM: Install 3/4" (19 mm) conduit.
Screw the pipe mount attachment onto the 3/4" (19
mm) conduit. Attach the adhesive backed gasket to
the top of the 105PM pipe mount attachment, being
careful to line up the holes in the gasket with the
mounting holes in the outlet box as shown in Figure
2.
4. Mount 105XBRi Series as follows. Unscrew the gasketed
base from the lens assembly as shown in Figures 1 and
2 and remove the clear gasket from around the base.
5. Secure the base to the appropriate mounting attachment
using four screws (supplied). Replace the clear gasket