Model MCX-32

Model MCX-32 Instruction Manual

Rev. 2.3

Page 33 of 49

Figure 37 Change Range Entry

Analog Out
The Analog Out field is set to ‘ON’ or ‘OFF’. Unless there is and AO-4 associated with this channel, this field
should be left as ‘OFF’. To turn on the Analog Out, select the Analog Out field on the screen, and the
controller will change the status from ‘OFF’ to “ON’ or from ‘ON’ to ‘OFF’.

Device Type
The Device Type field will either display the type of sensor connected, or the type of I/O Module (DA-4 or
DI-4). If the Auto Configure did not find a Detcon Model 100, 600D, 600 or 700 series sensor, this field will
display ‘Model 700’ as the default value. To change the device type, select the Device Type field and select
the correct type of sensor or I/O module. If the sensor is connected to a DA-4 module, select DA-4, if the
sensor or device is connected to a DI-4 I/O Module, select the DI-4. If the sensor is a Detcon Model 100,
600D, 600 or 700 series sensor connected via the Modbus™, select either 100, 600D, 600 or 700, respectively.

Figure 38 Device Type Selection

NOTE: If the Channel is set to ON, the controller will automatically attempt to communicate
with the device connected. If communication is not established, the controller will take the
channel into a “FAULT” (communication fault) condition.

Status
The Status is read from the sensor or I/O Module, and cannot be changed.