6.3.5

Alarm Test Mode

When selected, ALARM TEST MODE menu button will simulate alarm conditions by incrementing the gas
readings from 0 for all active gas channels at 5% full scale. Once the concentration has reached full scale, the
concentration will begin to decrement back to 0 and the controller will exit the test mode. The test mode can
also be terminated at any time during the test cycle by selecting the ALARM TEST MODE menu button
again.

As the readings cross their respective ALM1, ALM2, and ALM3 set points, the relays will fire

according to their configuration.

Figure 22 Alarm Test Mode

The on/off status of the test will be indicated on the ALARM TEST MODE menu button as well as on the
main display which will display ALARM TEST at the top when the function is active.

6.3.6

Modbus Address Screen

The Modbus Address Screen allows the setting of the address used for the Slave RS-485 Port (Port 3). This
address should normally be set for address 1, but can be changed via this screen.

Figure 23 Modbus Address Screen