Model PI-700 0-500ppb

PI-700 0-500ppb Instruction Manual

Rev. 0.0

Page 23 of 53

will not clear until the fault condition has been cleared. The sensor should be considered as ‘Out-of-Service’
until a successful AutoSpan calibration is performed.

Zero Fault

If the sensor drifts to < -10% of range, an “Under-Range Fault” will be declared. An “Under-Range Fault”
will cause a “Fault Detected” message to flash intermittently on the ITM display. The Modbus™ fault register
bit for Under-Range Fault will be set and will not clear until the fault condition has been cleared. If an Under-
Range Fault occurs, the 4-20mA signal will be set at 0mA until the fault condition is resolved.

Sensor Fault

If the intelligent plug-in sensor is not plugged in, plugged in incorrectly, or there is a communication failure, a
“Sensor Fault” is declared. A “Sensor Fault” will cause a “Fault Detected” message to flash intermittently on
the ITM display. The Modbus™ fault register bit for Sensor Fault will be set and will not clear until the fault
condition has been cleared. If a Sensor Fault occurs, the 4-20mA signal will be set at 0mA until the fault
condition is resolved.

Processor Fault

If the detector has any unrecoverable run-time errors, a “Processor Fault” is declared. A “Processor Fault”
will cause a “Fault Detected” message to flash intermittently on the ITM display. The Modbus™ fault register
bit for Processor Fault will be set and will not clear until the fault condition has been cleared. If a Processor
Fault occurs, the 4-20mA signal will be set at 0mA until the fault condition is resolved.

Memory Fault

If the detector has a failure in saving new data to memory, a “Memory Fault” is declared. A “Memory Fault”
will cause the “Fault Detected” message to flash intermittently on the ITM display. The Modbus™ fault
register bit for Memory Fault will be set and will not clear until the fault condition has been cleared. If a
Memory Fault occurs, the 4-20mA signal will be set at 0mA until the fault condition is resolved.

4-20mA Loop Fault

If the detector measures a 4-20mA loop load resistance > 1000 ohms, a “Loop Fault” is declared. A “Loop
Fault” will cause the “Fault Detected” message to flash intermittently on the ITM display. The Modbus™
fault register bit for Loop Fault will be set and will not clear until the fault condition has been cleared. If a
Loop Fault occurs, the 4-20mA signal will be set at 0mA until the fault condition is resolved.

Input Voltage Fault

If the detector is currently receiving an input voltage that is outside of the 11.5-28VDC range, an “Input
Voltage Fault” is declared. An “Input Voltage Fault” will cause the “Fault Detected” message to flash
intermittently on the ITM display. The fault register bit for Input Voltage Fault will be set and will not clear
until the fault condition has been cleared. If an Input Voltage Fault occurs, the 4-20mA signal will be set at
0mA until the fault condition is resolved.

Temperature Fault

If the detector is currently reporting an ambient temperature that is outside of the –40C to +75C range, a
“Temperature Fault” is declared. A “Temperature Fault” will cause the “Fault Detected” message to flash
intermittently on the ITM display. The Modbus™ fault register bit for Temperature Fault will be set and will
not clear until the fault condition has been cleared. If a Temperature Fault occurs, the 4-20mA signal remains
operational.