beautypg.com

4 pressure measurement sequence (gage only unit) – Condec UPC5110 User Manual

Page 9

background image

6

UPC5100/UPC5110 Operation & Maintenance Manual

The display scaling for these current measurements are as follows:

NOTE: UPC5100/UPC5110 reads a 4-20 mA signal only, but will display as either 4-20 mA or 20-100 mV.

The test cable connector wiring is as follows:

NOTE: Connector pin designations are for reference only, and are no longer a connector on newer units. See Figure 2-2
on page 5 (14).

2.4

Pressure Measurement Sequence (Gage Only Unit)

NOTE: See Figure 2-3 on page 5 when following these steps:

1. Turn the

MODE SELECT

valve (10) to the

PRESSURE

position.

2. Close the

COARSE ADJUSTMENT

valve (2), clockwise, and open the

VENT

valve (8),

counter-clockwise.

3. Using the

PRESSURE LIMIT CONTROL

regulator (1), (pull knob outward while adjusting) adjust the

maximum system input pressure (as read by the

PRESSURE LIMIT MONITOR

[9]), to any desired value

higher (typically 20-50% higher) than the full-scale range of the device under test. Using this technique,
the device under test is fully protected from being accidentally over-pressurized.

4. Zero unit by momentarily depressing the

ZERO

switch (12) for less than five seconds.

NOTE: The instrument can be zeroed at any time, as long as the VENT valve (8) is open, by momentarily depressing the
ZERO switch (12) for less than five seconds.

5. To apply pressure, close the

VENT

valve (8), approximately two turns clockwise, until it stops, then open

the

COARSE ADJUSTMENT

valve (2) approximately 1/2 turn counter-clockwise until the numerical

display begins to move. The operator may change the pressure rapidly until reaching approximately 90%
of the desired final value.

6. Use either the

COARSE ADJUSTMENT

(2) or

VENT

valve (8) to obtain a specific pressure reading. Both

provide precise control. As the pressure approaches the desired value, the valve being used for control
should be rotated slowly clockwise to its closed position.

7. To obtain exact pressure readings, slowly rotate the

VERNIER

control (13) knob in the direction required

(clockwise to increase pressure) as indicated by the electronic numerical display.

8. The transducer current measurement can be displayed at any time by placing the

DISPLAY SELECT

switch (16) in its

CURRENT

position.

SWITCH POSITION

DISPLAY READING

Current

0-20.000 mA by 0.005 mA

*Voltage

0-100.00 mV by 0.02 mV

Table 2-1. Display Select Switch (16)

CONNECTOR PIN DESIGNATION

FUNCTION

A

+ VDC

B

+ SIGNAL

C

NOT USED

D

VOLTAGE & SIGNAL COMMON

Table 2-2. Transducer Test Cable (PN 55092)

This manual is related to the following products: