Safety notices, Nebs requirements, Table 26 – Brocade VDX 8770-8 Hardware Reference Manual User Manual
Page 114

94
Brocade VDX 8770-8 Hardware Reference Manual
53-1002564-04
Safety notices
A
Safety notices
When using this product, observe the danger, caution, and attention notices in this manual. The
notices are accompanied by symbols that represent the severity of the safety condition.
NOTE
Translated safety notices are in the Brocade Product Safety Notices publication, which is available
on
.
The danger and caution notices are listed in numerical order based on their IDs, which are
displayed in parentheses, for example (D004), at the end of each notice. Use this ID to locate the
translations of these danger and caution notices in the Brocade Product Safety Notices.L
NEBS requirements
lists the installation requirements for meeting the NEBS GR-1089 compliance.
TABLE 26
NEBS installation requirements for the Brocade VDX 8770-8
Reference
Warning, requirement, or statement
Intrabuilding or Intra-connection
WARNING: The intra-building copper Ethernet ports of the equipment or
subassembly are suitable for connection to intrabuilding or unexposed
wiring or cabling only. The intra-building ports of the equipment or
subassembly MUST NOT be metallically connected to interfaces that
connect to the outside plant (OSP) or its wiring. These interfaces are
designed for use as intra-building interfaces only (Type 2 or Type 4 ports
as described in GR-1089-CORE, Issue 6) and require isolation from the
exposed OSP cabling. The addition of Primary Protectors is not sufficient
protection in order to connect these interfaces metallically to OSP wiring.
First Level Lightning Criteria AC Power
Ports
WARNING: The Brocade VDX 8770-8 must be connected to external
Special Protection Devices (SPD) when installed and connected to
commercial AC power.
Class A2 Voltage Accessibility
The Brocade VDX 8770-8 must be located in a restricted access location
were only crafts personnel are allowed access.
Class B Voltage Accessibility
The Brocade VDX 8770-8 must be located in a restricted access location
were only crafts personnel are allowed access.
Equipment Grounding Systems
The Brocade VDX 8770-8 must be installed and connected to the CBN,
IBN, or Ether.
Communication Equipment Grounding
The Brocade VDX 8770-8 is suitable for connection to the Central Office.
Bonding of Battery Return (BR) Input
Terminals
The battery returns of the Brocade VDX 8770-8 must be connected
(DC-I).
Connections
The Brocade VDX 8770-8 must be grounded via a copper ground
conductor.
Connections
All bare grounding connection points to the Brocade VDX 8770-8 must
be cleaned and coated with an antioxidant solution before connections
are made.
Connections
All surfaces on the Brocade VDX 8770-8 that are un-plated must be
brought to a bright finish and treated with an antioxidant solution before
connections are made.