Xb sets the burnout – Yokogawa DR240 User Manual
Page 68

6-14
IM DR231-11E
KEY_LOCK_ON
Key lock is turned on.
MATH_START
Starts computation.
MATH_CLR_START
Clears computation results then re-start
computation.
MATH_STOP
Stops computation.
MATH_ACK
Clears the computation status indication.
REPORT_START
Starts report.
REPORT_STOP
Stops report.
REP_RECALL_START
Starts printing the report.
REP_PRINT_STOP
Stops printng the report.
KEY_LOCK_OFF
Key lock is turned off.
S/U_LIST_START
Setup list printing starts.
S/U_LIST_STOP
Setup list printing is stopped.
MSG_PRINT
Message printing begins.
ALM_BUF_CLEAR
Alarm buffer is cleared.
MSG_BUF_CLEAR
Message buffer is cleared.
RAM_INIT
Internal memory is initialized.
COMM_INF
Information on communication module
parameter
MODULE_INF
Module information
RE_SYSTEM (DR232/DR242 only)
Reconstruction of a system
ALL_ITEM
All items of parameter p1
p2
Type of screen
OFF
No display on the function screen
FUNC1 Screen that appears when the
FUNC key is pressed.
FUNC3 Screen that appears when the
FUNC key is pressed for 3
seconds.
INIT
Initialize.(Effective only when p1
is set to ALL_ITEM.)
Example
Display setup list printing start on the FUNC1
screen.
XFS/U_LIST_START, FUNC1
Comments
• More than one function can be displayed on each
function screen.
• A function can be easily executed by being
displayed on the function screen.
XS
Sets which settings are to be
displayed on the setting screen.
Mode
Setup mode
Setting
XSp1, p2
p1
Contents to be displayed on the set screen
SYSTEM: System settings
UNIT
Unit settings
MATH
Settings for computation of
respective computation
channels
CONST
Settings for computation
constants
MEMORY
Settings relating to data
saving/reading in the built-
in RAM disk
FLOPPY
Settings relating to data
saving/reading on floppy
disks
ZONE
Zone recording settings
PARTIAL
partially expanded record
settings
CHART2
Second chart speed settings
TAG
Tag settings
TIMER
Timer settings
LOGIC
Logic settings
MESSAGE
Message settings
GROUP
Group settings
TREND
Turning on or off analog
records for each channel
DIGITAL_PR
Turning on or off digital
records for each channel
LIST_PR
Turning on or off list
printing for each channel
MANUAL_PR Turning on or off manual
printing for each channel
SCALE_PR
Turning on or off scale
printing for each channel
ALARM_PR
Turning on or off alarm
printing for each channel
HEADER
Header settings
TITLE
Title settings
MOVE_AVE
Moving average settings
INTERPOL
Step interpolation settings
MATCH_TIME Match time settings
LIST_FMT
List printing format settings
COPY
Copy contents settings
DST
Summer/winter time
ALL_ITEM
All items of parameter p1
p2
Type of screen
OFF
Nothing appears on the set screen.
SET
Screen when the set key is pressed
SET3 Screen when the set key is pressed for
3 seconds
INIT Initialize. (Effective only when p1 is
set to ALL_ITEM.)
Example
Show the settings of a tag on the screen for which
you have pressed the SET key.
XSTAG, SET
Comments
• More than one setting item can be displayed on
the set screen.
• By displaying a setting item on the set screen, the
setting item can be easily set.
• MATH in parameter p1 is valid only for recorders
with the optional computing function or floppy
disk drive function.
• CONST is valid only for recorders with the
optional computing function.
• MEMORY and FLOPPY are valid only for
recorders with the floppy disk drive function.
XB
Sets the burnout.
Mode
Setup mode
Setting
XBp1, p2
p1
Channel number (001 to 560)
p2
Selection of burnout
OFF
UP
Upscale traveling beyond the scale
DOWN Downscale traveling beyond the scale
Example
Set channels 01 to 10 of subunit 0 to upscale
burnout.
XB001-10, UP
Comments
• If channels are to be set successively, the setting is
effective only when the channels are in the same
unit.
6.5 Other Settings