Sb sets whether interpolation is performed or not, Pt turns on or off every channel of trend record – Yokogawa DR240 User Manual
Page 62

6-8
IM DR231-11E
Example
Print the range list and alarm list but do not print the
parameter list related to printing or the other
parameter list.
SFON, ON, OFF, OFF
SB
Sets whether interpolation is
performed or not.
Mode
Operation mode
Setting
SBp1, p2
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON/OFF
Example
Perform step interpolation for channel 6 in slot 3 of
subunit 4.
SB436, ON
Comments
• If step interpolation is performed, the space
between recorded points is recorded .
• If two or more channels are step-interpolated in
the same position, the recording priority depends
on the recording color, and recording is done in
the following order:
Black > blue-purple > magenta > navy blue > red
> blue > brown > green > orange > yellow-green
For example, if two channels being recorded in
black and in blue are step-interpolated in the same
position, the overlapped parts are recorded in
black.
• The optional computation channel number for a
stand-alone model is A01 to A30.
PT
Turns on or off every channel of trend
record.
Mode
Operation mode
Setting
PTp1, p2
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON/OFF
Example
Turn on the analog recording of channel 6 in slot 3 of
subunit 4.
pT436, ON
Comments
• The optional computation channel number for a
stand-alone model is A01 to A30.
PD
Turns on or off every channel of
digital records.
Mode
Operation mode
Setting
PDp1, p2, p3
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON
Records.
OFF
Does not record.
p3
1 to 6
timer number (recording interval:
Effective only when digital records are set
for “multiple”)
Example
Perform digital recording of channel 6 in slot 3 of
subunit 4 at the interval of timer 2.
pD436, ON, 2
Comments
• The optional computation channel number for a
stand-alone model is A01 to A30.
PM
Turns on or off every channel of
manual printing.
Mode
Operation mode
Setting
PMp1, p2
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON/OFF
Example
Perform manual printing for channel 6 in slot 3 of
subunit 4.
PM436, ON
Comments
• The optional computation channel number for a
stand-alone model is A01 to A30.
PA
Turns on or off the alarm printing for
every channel level.
Mode
Operation mode
Setting
PAp1, p2, p3, p4
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
Level (1 to 4)
p3
OFF
No alarm printing
ON1
Printing when an alarm is generated
ON2
Printing when an alarm is generated
or reset
p4
Selection of additional message
OFF
Does not print an additional message.
01 to 20
Message number
Example
When an alarm of level 2 of channel 6 in slot 3 of
subunit 4 is generated, print the alarm and message
No. 5.
PA436, 2, ON1, 05
Comments
• When an alarm is generated or reset, the alarm
generation time or alarm type is printed.
• If an additional message is specified, the message
set with the SG command is also printed.
• The optional computation channel number for a
stand-alone model is A01 to A30.
PC
Turns on or off scale printing for
every channel.
Mode
Operation mode
Setting
PCp1, p2
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
OFF
No scale printing
ON1
Printing for every 20% of the scale
length
ON2
Printing at 0% and 100% of the scale
length
ON3
Printing at 0%, 50%, and 100% of
the scale length
Example
Print the scale of channel 6 in slot 3 of subunit 4 at
positions 0%, 50% and 100%.
PC436, ON3
Comments
• For a channel for which recording is done in
partially expanded recording, the following
applies regardless of the p2 setting:
If the recording width is 100 mm or more, printing
is carried out at positions 0%, 100% and at a point
on the partially expanded recording boundary.
If the recording width is less than 100 mm but 50
mm or more, printing is carried out at positions
0% and 100%.
If the recording width is less than 50 mm, printing
is not carried out.
• This is effective for analog recording channels.
• A channel whose recording width is less than 50
mm is not printed.
• If ON1 is set to a channel whose recording width
is less than 150 mm, the setting is invalid. Printing
is carried out at positions 0%, 50% and 100%
only.
6.4 Setting the Recording