Flow Chart of Connections and Operation
The flow of procedures described in this operation guide is shown below. This flow
assumes that all connections have been made.
Performing the Loop
Back Test, Read Test,
and Write Test*
Perform the test
execution**
Run GateCONTROL
as a process
Run GateWT as
a process
Logging data from the temperature
controller, WT210, MX100, or recorder
on DAQLOGGER
Logging and saving data
using AddMulti
See pages 31
and 32
See page 36
Set up the WT210
See page 29
See page 33
Set up GateCONTROL
Set up GateWT
See page 30
See page 35
Set up the MX100
See page 38
Executing GateMX/MW
See page 43
See page 32
See page 36
See page 44
See page 51
Check the communication
conditions of the recorder
• Ethernet (IP address
and host name)
• COM1-COM9
(address)
Set up the temperature
controller
* GateCONTROL Loop Back Test, Read Test, and Write Test
GateCONTROL allows you to perform loop back tests on any temperature
controllers connected to it.
If the loop back test results in anything other than OK, it may indicate a problem
in the wiring of the communication cable, or a mismatched baud rate, parity, or
Modbus address.
Also, by performing a test acquisition you can determine whether the data set for
each tag is correct.
** GateWT Test Execution
During GateWT’s test acquisition, data is read from WT output channels assigned
to each tag and displayed as digital values. This allows you to determine whether
the communication settings for each tag are correct.