<4. Diagnostics>

4-3

IM 01C25R05-01EN

Integral

Indicator

DTM

display

Status

group

Cause

Countermeasure

Value and Status (Data Quality and Limit Status)

Differential

Pressure

(DP)

Static

Pressure

(SP)

External

Temperature

(ET)

DP %

SP %

ET %

AL.10

PRESS

P outside

limit

3

Differential

pressure

is outside

measurement

range limit of

capsule.

Check input

or replace

capsule when

necessary.

Value:

Measured value

Status:

Poor Accuracy and

Not Limited

(0x40)

Value:

Measured

value

Status:

Good and

Not Limited

(0xC0)

Value:

Measured value

Status:

Poor Accuracy and

Not Limited

(0x40)

Value:

Measured

value

Status:

Good

and Not

Limited

(0xC0)

AL.11

ST.PRSS

SP outside

limit

Static pressure

exceeds limit.

AL.12

CAP.TMP

CT outside

limit

Capsule

temperature is

outside range

(–50 to 130°C).

Use heat

insulation or

make lagging

to keep

temperature

within range.

AL.13

AMP.TMP

AT outside

limit

Amplifier

temperature is

outside range

(–50 to 95°C).

Value: Measured value

Status: Good and Not Limited

(0xC0)

Value: Measured value

Status: Good and Not Limited

(0xC0)

AL.14

EXT.TMP

ET outside

limit

External

temperature is

outside range.

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Measured

value

Status:

Poor

Accuracy

and Not

Limited

(0x40)

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Measured

value

Status:

Poor

Accuracy

and Not

Limited

(0x40)

AL.15

EXT.TMP

OHM

outside

limit

External

temperature

sensor

resistance is out

specification.

AL.30

PRS.RNG

P over

range

4

Differential

pressure

exceeds

specified range.

Check input

and range

setting, and

change them

as needed.

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Hold value

Status:

Bad and

Constant

(0x30)

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

AL.31

SP. RNG

SP over

range

Static pressure

exceeds

specified range.

Value:

Measured

value

Status:

Good

and Not

Limited

(0xC0)

Value:

Hold value

Status:

Bad and

Constant

(0x30)

Value:

Measured

value

Status:

Good

and Not

Limited

(0xC0)

AL.33

ET. RNG

ET over

range

External

temperature

exceeds

specified range.

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Hold value

Status:

Bad and

Constant

(0x30)