3.5 Setting
Set to the I/O parameters in the controller by using a teaching tool.Place the controller's
AUTO/MANU switch in the MANU position.The versions of teaching tool compatible with
EtherNet/IP are as follows:
Ɣ XSEL PC software : from V9.00.00.00
Ɣ SEL-T/TG
: from V1.12
Ɣ IA-T-X/IA-T-XD
: from V1.52
3.5.1 Parameter Setting
[1] Check of Network Module Type
Confirm that the 1
st
digit of I/O Parameter No.225 Network I/F Module Control setting is
showing “7” (EtherNet/IP).
No.
Parameter name
Default
(reference)
Input Range
Unit
Remarks
225 Network I/F Module Control
Referring
only
0H to
FFFFFFFFH
-
Bit 0 to 3: Type of Network I/F Module
Control 1
0: Not Mounted,
1: CC-Link,
2: DeviceNet,
3: Profibus,
4 to 5: System Reservation,
6: EtherCAT,
7: EtherNet/IP
The setting of this parameter is established at the delivery. For EtherNet/IP, it is shown as “7h”.
The value to be shown may differ depending on the construction of used option board.
[2] IP Address Setting
Set the IP Address to I/O Parameter No.132 to 135.
No.
Parameter name
Default
(reference)
Input Range
Unit
Remarks
132 Network I/F Module 1
Self IP Address (H)
192
1 to 255
- * Prohibited to set to 0 and 127
133 Network I/F Module 1
Self IP Address (MH)
168
0 to 255
-
134 Network I/F Module 1
Self IP Address (ML)
0
0 to 255
-
135 Network I/F Module 1
Self IP Address (L)
1
1 to 254
- * Prohibited to set to 0 and 255
Pay attention to avoid duplication of IP address.
[3] Subnet Mask Setting
Set the subnet mask to I/O Parameter No.136 to 139.
No.
Parameter name
Default
(reference)
Input Range
Unit
Remarks
136 Network I/F Module 1
Subnet Mask (H)
255
0 to 255
-
137 Network I/F Module 1
Subnet Mask (MH)
255
0 to 255
-
138 Network I/F Module 1
Subnet Mask (ML)
255
0 to 255
-
139 Network I/F Module 1
Subnet Mask (L)
0