5.2 EXPANDED SYSTEM REQUIREMENTS

*Use with resistor kit

5.3 OPTIONAL ITEMS FOR BOTH BASIC AND EXPANDED SYSTEM

SlimZone Deluxe

4

ITEM

QUANTITY

DESCRIPTION

2701-003

1 or 2

2 Zone Expander Board

Zone Thermostat

1 per Zone

Single Stage Electro-
mechanical* or Electronic

Motorized Zone Damper 1 per Zone Minimum

24VAC, 2 or 3 Wire

Damper Transformer

1 Minimum

24VAC, 12 VA per
Zone Damper**

ITEM

QUANTITY

DESCRIPTION

Outdoor Thermostat

1

Thermostat must close

for HiBP

connection when the out-
door temperature is above
the setpoint temperature.

Outdoor Thermostat

1

Thermostat must close

for LoBP

connection when the out-
door temperature is below
the setpoint.

Low Limit Duct Switch

1

Sensor must close the
connection when the
temperature is below the
setpoint.

High Limit Duct Switch

1

Sensor must close the
connection when the
temperature is above the
setpoint.

Clock

1

A timing device that closes
the contacts when the
system is switched into
unoccupied mode.

Smoke Detector

1

Smoke detector that will
close the contacts when
smoke is detected.

**More than one zone damper can be wired to a transformer as long as it has

an acceptable VA rating. For example, 3 zone dampers would require a
24VAC, 40VA transformer