TROUBLESHOOTING GUIDE

27.

LOGIC PANEL SPECIFICATIONS

Panel Power Requirements

Dedicated 24 VAC, 24VA Transformer

Minimum Power Consumption

250mA (Master Board Only)

Maximum Power Consumption

400mA (Master + 2 Expander Boards)

Maximum Current to Dampers

2.50 amps @ 68ºF (20ºC)

Functional Ratings

14˚F to 158˚F (-10˚C to 70˚C)

Storage Ratings

-4˚F to 158˚F (-20˚C to 70˚C)

NOTE: It is recommended that the logic panel be installed in a condi-
tioned environment. If installed in an unconditioned space, the current
limiting devices used in the panel are temperature dependent. The fol-
lowing linear relationship exists between the ambient temperature and
the operating current.

SlimZone Deluxe

28

PROBLEM

POSSIBLE CAUSE

SOLUTION

No heating/cooling

Zone thermostat(s)

Set COOL/OFF/HEAT

in house

switch on the thermostat(s)
to the proper setting.

Faulty heating/cooling

Troubleshoot equipment

Equipment

according to manufacturer’s
instructions.

Faulty thermostat

Troubleshoot thermostat
according to manufacturer’s
instructions. Replace if
necessary.

Faulty zone control
panel (NORMAL LED not

Replace if necessary.

flashing)
Improper remote switch

Ensure the switch is set

selector setting

to a mode of operation

(if installed)

that allows the requested call
to be serviced.

No heating/cooling

Balancing damper closed

Check all balancing dampers

in zone

in the same duct as the motor-
ized zone damper; closed bal-
ancing dampers should be
readjusted.

Zone registers closed

Check all zone registers;
closed registers should be
readjusted.

Faulty thermostat

Troubleshoot thermostat
according to manufacturer’s
instructions. Replace if
necessary.

Faulty zone control panel

Replace if necessary.

(NORMAL LED not flashing)