Robertshaw SlimZone Deluxe ZONE CONTROL SYSTEM User Manual
Page 32

26.
TROUBLESHOOTING GUIDE
27.
LOGIC PANEL SPECIFICATIONS
Panel Power Requirements
Dedicated 24 VAC, 24VA Transformer
Minimum Power Consumption
250mA (Master Board Only)
Maximum Power Consumption
400mA (Master + 2 Expander Boards)
Maximum Current to Dampers
2.50 amps @ 68ºF (20ºC)
Functional Ratings
14˚F to 158˚F (-10˚C to 70˚C)
Storage Ratings
-4˚F to 158˚F (-20˚C to 70˚C)
NOTE: It is recommended that the logic panel be installed in a condi-
tioned environment. If installed in an unconditioned space, the current
limiting devices used in the panel are temperature dependent. The fol-
lowing linear relationship exists between the ambient temperature and
the operating current.
SlimZone Deluxe
28
PROBLEM
POSSIBLE CAUSE
SOLUTION
No heating/cooling
Zone thermostat(s)
Set COOL/OFF/HEAT
in house
switch on the thermostat(s)
to the proper setting.
Faulty heating/cooling
Troubleshoot equipment
Equipment
according to manufacturer’s
instructions.
Faulty thermostat
Troubleshoot thermostat
according to manufacturer’s
instructions. Replace if
necessary.
Faulty zone control
panel (NORMAL LED not
Replace if necessary.
flashing)
Improper remote switch
Ensure the switch is set
selector setting
to a mode of operation
(if installed)
that allows the requested call
to be serviced.
No heating/cooling
Balancing damper closed
Check all balancing dampers
in zone
in the same duct as the motor-
ized zone damper; closed bal-
ancing dampers should be
readjusted.
Zone registers closed
Check all zone registers;
closed registers should be
readjusted.
Faulty thermostat
Troubleshoot thermostat
according to manufacturer’s
instructions. Replace if
necessary.
Faulty zone control panel
Replace if necessary.
(NORMAL LED not flashing)