CONNECTING AC / DC POWER

NOTE: Connect power only after other connections are finished. Do not touch the live AC power terminals! The unit has
been designed with an isolated AC input. Thus, polarity is not a concern for the AC input. The chassis is plastic, therefore
earth ground is not used. For D.C. operation, connect + 12V to pin 7 and - D.C. to pin 8.

CONNECTING SENSOR INPUTS

These diagrams show how to hook typical input sensors to the unit. The unit supplies an unregulated 12 Volt (50mA)
output to power these sensors (Pin 7).

A valid pulse is one which makes a transition from the off-state (0 to 1V) to the on-state (4 to 30V): a positive going edge.
The input impedance is 10K Ohms to ground. The unit can be programmed from the front panel for slow switch closure
inputs up to 40Hz (select "Lo CPS"), or solid state switches (select "hi CPS") up to 9.99KHz. No rear terminal jumpers are
required. Use PNP (sourcing) type pulsers.

D08N

1 COMMON

2 N.O. (N.C./NPN)

3 COMMON

4 N.O. (N.C./NPN)

5 A INPUT

6 B INPUT

7 12 V OUTPUT/ + DC INPUT

8 - DC (GROUND)

9 RESET INPUT

10 NOT USED

11 AC INPUT

12 AC INPUT

D12P

COUNT

POWER

GROUND

COUNT

GROUND

POWER

A

RELAYS

B

*

* PULLUP RESISTANCE

4.7K TYPICAL

GND

+12V

STRIP CHART

RECORDER

TURBINE FLOWMETER

PULSE OUTPUT
PULSE OUTPUT

-

+

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- A INPUT

6- B INPUT

7- 12VDC OUT/+DC IN

8- -DC (GROUND)

9- RESET INPUT

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1 2 3 4

ON

SWITCH

TURBINE FLOWMETER

TYPICAL SENSOR HOOKUP

TYPICAL FLOW SENSOR HOOKUP