OUTPUT WIRING

The following diagrams detail the connection of the relay and analog output options. Each relay consist of a form A contact
(Normally Open). NPN transistor or Normally Closed contacts are available with solder jumpers (see Jumper Options).

SOLENOID (Single Stage)

Use Relay A (pins 1 & 2) for single stage preset. When the count or rate (selectable) reaches Preset A, Relay A will
energize. When Relay A closes, current passes through the solenoid for activation. When operating AC solenoids,
we recommend the use of an MOV to reduce inductive kickback (use a diode for DC solenoids).

ANALOG OUTPUT

The analog output can be selected to output 4-20 mA or 0-20 mA and can be selected to track the rate or count of
the C display. Pin 13 supplies 12 to 18V to power the current loop. Pin 14 supplies the current sinking driver.
When connecting a strip chart recorder, make connections as follows:

MOV
recommended

SOLENOID

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- A INPUT

6- B INPUT

7- 12VDC OUT/+DC IN

8- -DC (GROUND)

9- RESET INPUT

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1 2 3 4

ON

SWITCH

D08P

Prox Sensor

BLK

BRN
BLU

ALARMS

The relays can be used to trigger alarms which warn the operator that a batch is complete or the rate has
exceeded a set speed. The outputs are programmable to be assigned to the A,B or C rate/count. When
assigned to the count, the relays can have a user selectable on time (duration) or can be latched until reset.

LIGHT

BELL

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- A INPUT

6- B INPUT

7- 12VDC OUT/+DC IN

8- -DC (GROUND)

9- RESET INPUT

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1 2 3 4

ON

SWITCH

GND

+12V

STRIP CHART

RECORDER

TURBINE FLOWMETER

PULSE OUTPUT
PULSE OUTPUT

-

+

1- COMMON

2- N.O.(N.C./NPN)

3- COMMON

4- N.O.(N.C./NPN)

5- A INPUT

6- B INPUT

7- 12VDC OUT/+DC IN

8- -DC (GROUND)

9- RESET INPUT

10- NOT USED

11- A.C. INPUT

12- A.C. INPUT

RELA

YS

A

B

13- V+

14- I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1 2 3 4

ON

SWITCH

TURBINE FLOWMETER