The following is a list of abbreviations as they appear on the display and front panel of the unit.

ABBREVIATION

DESCRIPTION

FACTOR

SCALING FACTOR - For A and B Inputs. Each input has a separate 5 digit dividing scale factor.

DP F A

DECIMAL POINT FOR FACTOR A - Enter location of decimal point for scaling Factor A by pressing the
button under the digit where the decimal is desired.

DP F B

DECIMAL POINT FOR FACTOR B - Enter location of decimal point for scaling Factor B by pressing the
button under the digit where the decimal is desired.

COUNT

PORTION OF MENU FOR SETTING COUNTER VARIABLES AND “C” DISPLAY COMBINATIONS.

DP LOC

DECIMAL POINT LOCATION - Enter desired location of decimal by pushing the button under the digit
where the decimal is desired. Changing the decimal will change the decimal location in the A,B&C total
as well as the rate displays.

total

TOTAL - Allows the unit to display A ADD B or A SUBTRACT B (

a add b

or

a sub b

)

ratio

RATIO - Allows the unit to display A DIVIDED BY B X 100 to show percent of A to B or
A DIVIDED BY A PLUS B X 100 to show percent of A to A + B. (

A/B

or

A/A+B)

A SUB B

A SUBTRACT B - The number of scaled pulses from Input B are subtracted from the number of scaled
pulses from Input A. (-99999 TO 999999)

A ADD B

A ADD B - The number of scaled pulses from the A Input are added to the number of scaled pulses from the
B Input.

a / b

A DIVIDED BY B - The number of scaled pulses of input A are divided by the number of scaled pulses of
input B X 100 to give the percent ratio of A

÷

B.

a / a+b

A DIVIDED BY A PLUS B - The number of scaled pulses of input A divided by A plus the number of scaled
pulses of input B X 100 to give the percent ratio of A

÷

A + B.

RST al

RESET ALL - When the remote reset is negative edged triggered, A,B, & C total displays are reset to 0.
The reset button (rst) will only reset what is being displayed. If the C display is reset both A&B displays
are reset as well.

rsT 1

RESET ONE - Will give a chose between resetting the A or B total displays. If the A display is chosen and the
remote reset is negative edged triggered, only the A display is reset. If B display is chosen the same applies.
The C display will update accordingly. The reset button (rst) will only reset what is being displayed.
If the C display is reset both the A&B displays are reset as well.

HI CPS

HIGH COUNTS PER SECOND - This sets the unit to accept high count speeds (0-9.99KHz)

LO CPS

LOW COUNTS PER SECOND – This sets the unit for contact debounce filtering (0-40Hz)

RATE

PORTION OF MENU FOR SETTING RATE VARIABLES

RPS

RATE PER SECOND - The display will read in rate per second.

SCALE

SCALING - Allows unit to display rate per minute or rate per hour.

Z 60

DIVIDE K FACTOR BY 60 - This sets the unit for rate per minute; equal to 60 times rate per second.