Liquid Controls SP2850 (MS-649) User Manual
Page 16
Sponsler, Inc.
Model SP2850-TC with MS649
Page 16
DOC#: MN-2850
(Press D to display desired timebase)
ENT (selects displayed options)
K-FACTOR (Flashes, followed by existing K-Factor)
CLR
0 Flashes
1
1
D
6
8 (as an example)
11.68 Flashes
(Press
D
for decimal)
ENT
RUN MODE
Setting 16 Point Option for Non-linear Input: Reference `16 Point Linearization Option”
NOTE:
If TEST is entered, point data can be entered exactly as in selected time entries. However, when the unit
`runs’ in Test Mode `K-Factor’ is always 1. `Rate’ (R) displays frequency (inputs per sec.). Counter displays 1 count
per each input.
Press
Display
D
MENU Flashes then PRESET
↓
D until
16POINT
↓
ENT
LN
↓ 16PT↓ (LN: Linear 16PT: 16 point)
(Press D for 16 point)
ENT
MINUTES
↓
D
HOURS
↓
D
TEST
↓
D
SECONDS
↓
(Press D to go to minutes)
ENT (selects displayed option)
POINT 00 (Enter point 00 to go to run mode)
1
(selects point 1)
POINT 01 (Key in point desired)
ENT
F # # (Shows frequency in memory)
CLR
F 0
1
0
0 (as an example)
F 100 (Frequency for point 1 is 100)
ENT
K # # (Shows K-Factor in memory)
CLR
K 0
1
0
0 (as an example)
K 100 (K-Factor for point 1 is 100)
2
POINT 02 (Enter point data as desired)
(Repeat through 16 points)
CLR
POINT 00 (Enter point 00 to exit setup)
ENT
RUN MODE