DEFINITION OF MENU PROMPTS
MENU- This prompt is displayed when the programming menu is entered.
PRESET- This sets the value at which the preset A will drop out (R0, reset to 0 mode). In the ‘SP’ (set to preset
mode) the unit will reset to this Preset value and count down to 0.
PREWARN- This value is the amount before the preset value that the Prewarn relay will drop out. For example: the
Prewarn relay is to drop out 10 counts before the Preset and the Preset is 1234, then set the Prewarn at 10
(not 1224). NOTE: If the Prewarn is larger than the Preset, the warning ‘PREWRONG’ will be displayed.
PRE TYP- (PRESET TYPE): This section of the menu allows the user to choose between ‘EZ PRE’ (easy preset) or
‘STD PRE’ (standard preset).
EZ PRE- (EASY PRESET): See ‘OPERATION USING EZ PRE’ pg.
STD PRE- (STANDARD PRESET): See ‘OPERATION USING STD PRE’ pg.
INHKEY(INHIBIT): Disables front panel START, STOP, MENU, ENT keys.
ENAKEY (ENABLE): Enables front panel START, STOP, MENU, ENT keys.
16 POINT- This section of the menu allows the user to select 16 point variable K-Factor data or linear K-Factor
programming.
16PT- (16 POINT); Enter this section to enter the 16 point setup procedure.
LN- (LINEAR); Enter this section to set up a linear K-Factor.
K-FACTOR- This is a scaling factor that converts the input into engineering units. Example: To total in gallons when
the meter is putting out 100 pulses per gallon, enter 100 for K-Factor.
TEST- When ‘TEST’ is selected, point data can be entered exactly as in selected time entries. However, when the
unit ‘runs’ in Test mode, K-Factor is always 1. ‘Rate’ (R) displays frequency (inputs per second). ‘Counter’ displays
1 count per each unit.
HOURS- When `hours’ is selected, the ratemeter will display units per hour.
MINUTES- When `minutes’ is selected, the ratemeter will display units per minute.
SECONDS- When `seconds’ is selected, the ratemeter will display units per second.
POINT ##- This prompt appears before each of the 16 points to be entered. To exit the 16 point set-up press `CLR’
then `ENTER’.
F#######- This prompt indicates the Frequency for each of the 16 points.
K#######- This prompt indicates the K-Factor for each of the 16 points.
COUNT- This section of the menu is used to set up the counter information.
R0- (RESET TO ZERO): When `R0’ is selected, the counter will reset to 0 (count up) when reset.
SP- (SET TO PRESET); When `SP’ is selected, the unit will reset to preset (count down) when reset.