beautypg.com

Electric wiring 8.4. circuit board, Electric wiring, Circuit board – Burkert Type 3003 User Manual

Page 19: English, Type 3003

background image

19

Rotary actuators with integrated emergency reset

Max. current

2.4 A

Charging time

14 h max

Feedback relay for charge state

24 V DC - 1 A max

Permitted ambient temperature

-10 °C - +40 °C

8.3.

electric wiring

65

F+

E-

66

17

18

17

18

Battery block

control and power

supply card

F+

Wire colour
red

E-

Wire colour
black

Load state

feedback

Loaded battery: closed
contact

1

2

3

1

2

3

D1

D2

Open

N

Ph

A

A

Ph

Open

KM1

N

A1

A2

N

24 V

AC/

DC

B

B

100V-240V 50/60 hz

(100V-350V dc)

15V-30V 50/60 hz

(12V-48V dc)

On / Off Mode

KM1 - Customer

contactor switch

Suggestet customer

wiring

Actuator

wiring

Total security mode

safety block

Fig. 11: Electric wiring

configuration a or B
A-standard mode: If the actuator is controlled with a programmable
controller, the feedback of the charge state can be connected to it.

B-mode - increased safety (if the feedback relay is used, terminals
65 and 66): The actuator does not actuate the valve unless the safety
block is loaded.

8.4.

circuit board

A

D

E

B

C

Fig. 12: Diagram: Circuit board

A 18 V DC connection

D Green LED*

B Battery block connection

E Red LED **

C Connection for feedback

(charge state)

english

Type 3003