English, 3 sens - setting the sensor input – Burkert Type 8624 User Manual
Page 25

8624-2 Standard - 23
english
6.6.3
SENS - setting the sensor input
Î Select here whether the sensor is to send 4 - 20 mA or 0 - 10 V to the
controller for the actual value of the controlled variable (factory setting: 0 -
10 V).
Î Next enter the scaling. The range corresponding to the standard signal (4 -
20 mA or 0 - 10 V) is set, i.e. the pressure or flow rate or another type of
controlled variable is entered at 4 mA or 0 V (lower limit) and at 20 mA or 10
V (upper limit).
Settings between 0.000 and 9999 are possible. The unit corresponds to the value
set in the menu item
UNIT.
(factory setting: S LO=0.00; S HI=10.00)
Example:
Lower limit (
S LO) 2,5 bar
4 mA
Upper limit (
S HI) 20 bar
20 mA
=> An actual value signal of 12 mA corresponds in this case to 11.25 bar
- Type 1062 (112 pages)
- Type 1050 (4 pages)
- Type 8750 (64 pages)
- Type 8750 (82 pages)
- Type 8681 (90 pages)
- Type 8681 (40 pages)
- Type 8798 (2 pages)
- Type 8791 (4 pages)
- Type 8798 (106 pages)
- Type 8792 (118 pages)
- Type 8791 (15 pages)
- Type 8792 (136 pages)
- Type 8792 (252 pages)
- Type 8718 (34 pages)
- Type 8791 (154 pages)
- Type 8791 (106 pages)
- Type 8791 (184 pages)
- Type 8791 (28 pages)
- Type 8791 (21 pages)
- Type 0911 (64 pages)
- Type 0911 (84 pages)
- Type 0911 (76 pages)
- Type 0911 (46 pages)
- Type 1058 (31 pages)
- Type 1060 (4 pages)
- Type 1066 (112 pages)
- Type 1067 (158 pages)
- Type 1077-2 (33 pages)
- Type 1094 (41 pages)
- Type 1094 (82 pages)
- Type 1094 (126 pages)
- Type 1094 (12 pages)
- Type 1115 (25 pages)
- Type 1150 (99 pages)
- Type 1541 (2 pages)
- Type 5142 (6 pages)
- Type 8619 (40 pages)
- Type 8619 (134 pages)
- Type 8620 (177 pages)
- Type 8622 (4 pages)
- Type 8623 (130 pages)
- Type 8623 (90 pages)
- Type 8625 (118 pages)
- Type 8718 (4 pages)