X.time, Limiting the control speed – Burkert Type 8791 User Manual

Page 47

background image

47

ConfiguringAuxiliaryFunctions

8.5.4.

X.TIME -
limiting the control Speed

Use this function to specify the opening and closing times for the entire stroke and thereby limit control speeds.

When the

X.TUNE function is running, the minimum opening and closing time for the entire stroke is auto-

matically entered for Open and Close. Therefore, movement can be at maximum speed.

Factory setting: values determined at the factory by the

X.TUNE function

If the control speed will be limited, values can be input for Open and Close which are between the minimum
values determined by the

X.TUNE and 60 seconds.

1

1

X.TIME

valve timeopen
valve timeclose

Fig. 40: X.TIME function

Valve timeopen: Opening time for entire stroke (in seconds)

Adjustment range: 1 – 60 seconds

Valve timeclose: Closing time for entire stroke (in seconds)

Adjustment range: 1 – 60 seconds

effect of limiting the opening speed when there is a jump in the set-point value

Set-point
value

Actual value

Open

t

Valve stroke [%]

Fig. 41: X.TIME graph