ParameterizationofBasicFunctions
7.2.2.
CHARACT -
Select the transfer characteristic between input signal
(position set-point value) and stroke
Characteristic (customer-specific characteristic)
Use this function to select a transfer characteristic with reference to set-point value (nominal position) and valve
stroke to correct the flow-rate or operating characteristic.
Factory setting: linear
The switching position of the DIP switches in the positioner takes precedence over the communication
software, i.e. settings of the correction characteristic (
CHARACT) that are modified through the communi-
cation software are only active if the corresponding DIP switch in the positioner is set to ON.
CHARACT
select characteristic curve
linear
linear
1 : 25
1 : 33
1 : 50
25 : 1
33 : 1
50 : 1
FREE
Fig. 24: CHARACT function
Select characteristic: Description:
linear
Linear characteristic
1 : 25
Equal percentage characteristic 1:25
1: 33
Equal percentage characteristic 1:33
1 : 50
Equal percentage characteristic1:50
25 : 1
Inversely equal percentage characteristic 25:1
33 : 1
Inversely equal percentage characteristic 33:1
55 : 1
Inversely equal percentage characteristic 50:1
FREE
4)
User-defined characteristic, freely programmable with nodes
4)
For information on entering nodes, see “Entering the freely programmable characteristic”