Operationandfunction
procedure:
To run
X.TUNE, the positioner must be in the AUTOMATIC operating state
(DIP switch 4 = OFF).
→
Set up connection
→
Set up TUNE in the navigation area
→
Start
X.TUNE. To do this, click "Start X.TUNE"
2)
.
The progress of
X.TUNE is shown in the communication software:
XTUNE start → POS 100 → ... → XTUNE end
When the automatic adjustment completes, the message "XTUNE end" appears
3)
.
The changes are automatically transferred to the positioner's memory (EEPROM) after the
X.TUNE function is
successful.
After
X.TUNE is complete, read the device parameter for processing from the positioner (see Chapter
“6.4.1. Reading Parameters from the Device”).
2)
X.TUNE can also be started by pressing the key 1 on the positioner and holding it for 5 seconds.
3)
If an error occurs, an error message appears (see Chapter “6.7. Error Messages”).