22

Configuration

9.3.1.

InP (Input) - Selection of the input signal

Enter the type of standard signal used in this menu item. You can select between the following standard signals:

• 0 ... 5 V,

• 0 ... 10 V,

• 0 ... 20 mA,

• 4 ... 20 mA.

Figure 15:

InP (Input) - Selection of the input signal

9.3.2.

Out (Output) - Valve settings

In this menu the electronics are adjusted to

• the valve used and

• the fluidic conditions in the application.

Absolutely vital are

• the setting of the valve type in the sub-menu VALV and

• the setting of the working range of the coil current in the sub-menu AdJ.

To ensure that the device functions perfectly, set the PWM frequency which is suitable for the valve.

• In the case of types 2871, 2873 and 2875 the PWM control frequencies must be adjusted in the VAdJ

submenu.

• In the case of special applications the PWM control frequency must be individually set in the VAdJ submenu.

If you have any queries, please contact your sales office or the Bürkert Technical Center. 24 h service
number: +49 (0) 7940 / 10 91 110

Set values for PWM frequencies:
A table of PWM frequencies which are suitable for controlling the valve type can be found on the Bürkert
homepage: www.burkert.com → Type 8605.