beautypg.com

Technical data, Operating conditions – Burkert Type 8605 User Manual

Page 11

background image

11

Technical Data

6.

TECHNICAL DATA

6.1.

Operating Conditions

WARNING!

The Type 8605 is not designed for use outdoors!

• Do not use the Type 8605 outdoors and avoid heat sources which may result in the permitted temperature

range to be exceeded.

Power supply

12...24V DC ± 10%
Residual ripple 5 %

Power consumption

ca. 1 W

Output current (on the valve)

max. 2 A

Operating temperature

-10 ... 60º C / 14 ...140ºF

Interference resistance

to EN50082-2

Emission

to EN50081-2

Current range, depending
on the version for valves

40 ... 220 mA,
200 ... 1000 mA,
500 ... 2000 mA

Standard signal input

Voltage (0 ... 5, 0 ... 10 V)

input impedance > 20 kW

Current (0 ...20, 4 ... 20 mA)

input impedance <200 W

Housing: DIN rail version

Degree of protection

IP40 (DIN EN 60529)

Materials

Polyamide / PBT

Dimensions

LxBxH: 97x27x57 mm

Housing: Cable plug version

Degree of protection

IP65 (DIN EN 60529)

Materials

Polyamide / PC

Dimensions

LxBxH: 70x32x42.5 mm

english

Type 8605