2 technical data 460v class, Product description – DE-STA-CO F5-B AC Inverter Drive User Manual

Page 8

background image

8

2.3.2 Technical Data 460V Class

1)

The wire gauge is based on the maximum fuse rating, copper wire with minimum 75°C insulation rating,

THHW or equivalent. If branch circuit protection is selected based on rated input current, the wire size could be
reduced.
2)

Rated operation means, rated input voltage, rated output current, and rated carrier frequency.

3)

This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")

4)

With units with integrated EMI filter the distance is less:
up to max. 5m line length and 4kHz operating frequency = Limit Value B (EN 55011)
up to max. 10m line length and 16kHz operating frequency = Limit Value A (EN 55022)

Product Description

Inverter Size

5

7

9

10

12

13

14

Recommended Motor Power

[hp]

1/2

1

2

3

5

7.5

10

Housing size

A

A

A

B

B

D

D

Input Ratings

Supply voltage

[V]

305...500 ±0 (460 V Nominal voltage)

Supply voltage frequency

[Hz]

50 / 60 +/- 2

Input phases

3

3

3

3

3

3

3

Rated input current

[A]

1.4

2.5

4.8

6.7

10.6

15.4

19.6

Recommended maximum input fuse

[A]

15

15

15

15

20

20

25

Recommended wire gauge

1)

[awg]

14

14

14

14

12

12

10

Output Ratings

Rated output power [kVA] 0.90

1.8

2.8

4.0

6.6

8.3

11.0

Rated motor power

[kW] 0.37

0.75

1.5

2.2

4.0

5.5

7.5

Rated output current

[A]

1.0

1.8

3.4

4.8

7.6

11.0

14.0

Peak current (30 seconds)

[A]

2.3

4.7

7.4

10.4

17.0

21.6

29.7

Over current fault (E.OC) trip level

[A]

2.8

5.6

8.9

12.5

21.0

25.9

35.6

Overload curve (see annex)

1

Output voltage

[V]

3 x 0…V Line

Output frequency

[Hz] Generally 1600Hz however it is limited by the

switching frequency

Rated switching frequency [kHz]

4

4

4

8

4

4

4

Maximum switching frequency [kHz]

4

4

4

16

4

16

4

Power loss at rated operation

2)

[W]

45

50

60

120

150

185

185

Stall current at 4kHz

[A]

1.3

2.6

4.1

5.8

7.6

12

14

Stall current at 8kHz

[A]

-

-

-

5.8

-

9.5

-

Stall current at 16kHz

[A]

-

-

-

4.9

-

5.8

-

Braking Circuit

Min. braking resistance

3)

[Ohm]

390

180

110

82

82

56

56

Typ. braking resistance

3)

[Ohm]

620

300

150

270

150

100

85

Max. braking current

[A]

2.2

4.5

7.5

10

10

15

15

Installation Information

Max. shielded motor cable length at 4 kHz

4)

[ft]

30

30

30

330

165

300

300

Max. shielded motor cable length at 8 kHz

4)

[ft]

-

-

-

165

300

-

Max. shielded motor cable length at 16kHz

4)

[ft]

-

-

-

100

300

-

Tightening torque for terminal strip [in lb]

Environmental

Max. heat sink temperature TOH

[°C]

90°C / 194°F

Storage temperature

[°C]

-25...70 °C / -13…158°F

Operating temperature

[°C]

-10...45 °C / 14…113°F

Housing design / protection

Chassis / IP20

Relative humidity

max. 95% without condensation

Approvals

Tested in accordance with…

EN 61800-3 /UL508C

Standards for emitted interference

EN 55011 Class B / EN 55022 Class A

Standards for noise immunity

IEC 1000-4-2 / -3 / -4 / -5/ -6

Climatic category

3K3 in accordance with EN 50178

4.5