beautypg.com

6 imc motors, 7 emi(ce) filters, Installation and connection – DE-STA-CO F5-B AC Inverter Drive User Manual

Page 20

background image

20

The above motors are also rated to operate on European 220V/380-50Hz or
230V/400V-50Hz systems. When operating on these types of voltage
supplies, parameter CP.5 must be set to 50.0 for proper motor operation.

3.3.6 IMC Motors

Installation and Connection

3.3.7 EMI(CE) Filters

The KEB COMBIVERT frequency inverters are optionally available with EMI filters. If
you have a 1/2, 1, 2 Hp 460VAC system your unit comes equipped with this item. These
filters allow the KEB COMBIVERT to meet CE EMC directive 89/339. All filters are
dimensioned for the inverter’s rated current and are designed to meet the conducted
emission limit as defined by EN55011/B.

The filter kits contain all required hardware for installation. The filters include the
sheilded supply wires which connect the filter to the inverter. Depending on the
available space and filter type, the filter can either be installed under the frequency
inverter (Back Mount), or beside the frequency inverter (Panel Mount).

Voltage

Class

Phases

Filter Kit

Mounts with

Inverter size

Style

Dimensions [in]

[HxWxL]

230 VAC

1

92C84982210000

05 & 07

Panel Mount

1.6x3.5x9.8

230 VAC

1

92C84982220000

09 & 10

Back Mount/Panel Mount

1.6x3.5x9.8

230 VAC

3

92C84982230000

12

Back Mount/Panel Mount

1.6x3.5x11.2

460 VAC

3

92C84982240000

10

Back Mount/Panel Mount

1.6x3.5x9.8

460 VAC

3

92C84982250000

12

Back Mount/Panel Mount

1.6x3.5x9.8

460 VAC

3

92C84982260000

13

Back Mount/Panel Mount

1.6x3.5x11.2

460 VAC

3

92C84982270000

14

Back Mount/Panel Mount

2.0x3.5x11.2

EMI (CE) Filters

Hp

Operating Voltage

Speed [RPM]

Mounting Configuration

Motor Part Number

1/8

230V/460V

1690

IEC 56-B14

92C81286010000

1/6

230V/460V

1685

IEC 63-B14

92C81286020000

1/4

230V/460V

1685

IEC 63-B14

92C81286030000

1640

IEC 71-B14 (square)

92C49952070000

1690

IEC 71-B14

92C49952080000

1685

IEC 71-B14

92C49953170000

1685

NEMA 56C

92C49953180000

1710

IEC 80-B14

92C49954080000

1710

NEMA 56C

92C49954090000

1710

IEC 80-B14

92C49955430000

1710

NEMA 56C

92C49955410000

1720

IEC 90-B14

92C49956230000

1720

NEMA 145TC

92C49956220000

1710

IEC 90-B14

92C49957340000

1710

NEMA 145TC

92C49957330000

1720

IEC 100-B14

92C49958240000

1720

NEMA 182TC

consult factory

4

230V/460V

1730

IEC 100-B14

92C81285010000

1735

IEC 112-B14

92C49959260000

1735

NEMA 182TC

92C49959280000

1720

IEC 112-B14

consult factory

1720

NEMA 213TC

consult factory

10

230V/460V

1750

IEC 112-B14

consult factory

1/3

230V/460V

1/2

230V/460V

3/4

230V/460V

1

230V/460V

1.5

230V/460V

2

230V/460V

7.5

230V/460V

3

230V/460V

5

230V/460V