3 motor connection, Installation and connection – DE-STA-CO F5-B AC Inverter Drive User Manual
Page 18
18
L3
++
--
PB
U
V
W
X1A
M
3~
L1
N/L2
T1
T2
PE
U
V
W
The maximum motor cable length listed in the tables in section 2.3 is based
on several factors: use of shielded motor cables, ground current limitations,
increased EMI noise levels, voltage peaks at the motor terminals.
Connect shield to the mounting
plate with maximum surface
area (use metal cable clamp)
Motor-temperature sensor is optional
(can be NC switch or PTC type sensor)
PA
PB
U
V
W
X1.B
M
3~
T1
T2
PE
U
V
W
PE
3.3.3 Motor Connection
The maximum
motor cable
length listed in
the tables in section 2.3
is based on several
factors: use of shielded
motor cables, ground
current limitations,
increased EMI noise
levels, voltage peaks at
the motor terminals.
Terminal X1B provides connections for:
•
++, PB
Braking resistor
•
U, V, W
Motor
•
T1, T2
Temperature sensor/Switch
NOTE: The T1/T2 terminals aren’t present on the 230
VAC A-housing inverters.
Installation and Connection
A Housing:
A Housing:
B & D Housings:
T2
T1
PB
PA
W
V
U
PE
-The PA, PB, T1, and T2 terminals aren’t present on the 230 VAC A-
Housing models.
-If terminals T1/T2 aren’t used a jumper needs to be installed between
them.
NOTE: If terminals T1/T2 aren’t used a jumper needs to be installed between them.