beautypg.com

Error diagnosis – DE-STA-CO F5-B AC Inverter Drive User Manual

Page 50

background image

50

A. EF

ABN.STOP external fault

90

Warning: external error. This will be shown on Quick Stop
condition.

A.ndOH no A. drive overheat

91

Warning: no more overtemperature of motor TEMPERATURE
SENSOR. Motor SENSOR is low-resistance again.

A.nOHI no A.STOP overheat int.

92

Warning: no more overtemperature in the interior

A.buS

ABN.STOP bus

93

Warning: Watchdog for communication between operator/
control card has responded

A.PRF ABN.STOP prot. rot. for.

94

Warning: locked direction of rotation clockwise

A.PRR ABN.STOP prot. rot. rev.

95

Warning: locked direction of rotation counterclockwise

A.dOH ABN.STOP drive over heat

96

Warning: overtemperature of motor TEMPERATURE SENSOR

A.OH2 ABN.STOP motor protect.

97

Warning: electronic motor protective relay has tripped

A.nOL no ABN.STOP overload

98

Warning: no more overload, OL counter has reached 0 %.

A. OL

ABN.STOP overload

99

Warning: Overload can only be reset at A.nOL, if OL counter
has again reached 0 %

A.OL2 ABN.STOP overload 2

100

Warning: Overload can only be reset at A.nOL2, if cool-down
time has elapsed

A.nOL2 no ABN.STOP overload 2

101

Warning: no more overload, the cool-down time has elapsed.

A.SET ABN.STOP set

102

Warning: set selection: It has been attempted to select a
locked parameter set.

Error Diagnosis