Alpha Technologies AlphaNet DSM Series DOCSIS User Manual
Page 38

38
745-814-B0-001, Rev. A
6.0
Data Management, continued
6.3
SCTE-HMS MIB Alarms, continued
6.3.1 SCTE-HMS Configurable Alarms, continued
Discrete Alarm Definitions and Common Settings
Discrete Alarms
Discrete Alarm
Value
Definition
Example
Settings
psInverterStatus
1
Inverter is off
Disable
psInverterStatus
2
AC Input line loss
EnableMinor
psInverterStatus
3
Inverter is in a local test cycle
Disable
psInverterStatus
4
Remote inverter test has been
initiated
Disable
psInverterStatus
5
The last Inverter test failed.
EnableMinor
psMajorAlarm
1
No alarm
Disable
psMajorAlarm
2
Service has been dropped or a
service interruption is imminent. This
is a general alarm; the cause of which
can be determined by looking in the
Discretes Table.
EnableMajor
psMinorAlarm
1
No alarm
Disable
psMinorAlarm
2
A non-service effecting condition has
occurred and should be monitored
EnableMinor
psTamper
1
Indicates status of enclosure door
tamper sensor: closed (door is open).
EnableMinor
psTamper
2
Indicates status of enclosure door
tamper sensor: open (door is closed).
Disable
psInputVoltagePresence
1
Digital value indicating that
line voltage is lost, based on
measurement of input voltage.
EnableMinor
psInputVoltagePresence
2
Indicates that line voltage is present
and within tolerance, based on
measurement of input voltage.
Disable
transponderInterfaceBusIdent
1
Remote device will respond to
commands from master transponder.
Disable
transponderInterfaceBusIdent
2
Local device is under local control and
will not respond to commands from
master transponder.
EnableMinor
transponderInterfaceBusIdent
3
Device is not responding.
EnableMajor
Table 6-5, Discrete Alarm Definitions and Common Settings