Alpha Technologies AlphaNet Series External DOCSIS User Manual
Page 26

26
745-838-B2-001 Rev. A
3.0
Installation Instructions for Specifi c Power Supplies, continued
3.3
Alpha AM/AP Series Power Supply, continued
3.3.2 Output Voltage Calibration
No calibration is necessary for the Alpha AM/AP power supply.
3.3.3. Provisioning the Transponder on the Network
The transponder must be recognized by the CMTS as a valid device and be able to
obtain an IP address and communicate with the SNMP management server.
Load the transponder’s MAC address into the CMTS.
1.
Setup SNMP using the two propriety MIBs fi les.
2.
Compile the two MIBs onto a network manager or MIB browser software.
3.
Set the MIBS points for the AM/AP as follows:
4.
Oid: 1.3.6.1.4.1.2183.2.3.3.1.2 set to (4) (power supply
selection)
Oid: 1.3.6.1.4.1.2183.2.3.6.5 set to (3) (acNormal for
output voltage measurement)
Oid: 1.3.6.1.4.1.2183.2.3.6.6 set to (1)for 110V powered
supply or (2) for 220V (input voltage measurement)
See Section 4.0, Proprietary Management Information Bases (MIBs) for detailed
information.
Install and confi gure the DOCSIS confi guration fi le. See Section 2.1.9 for a
5.
sample fi le.