3.0 Installation Instructions for Specifi c Power Supplies, continued
3.3 Alpha AM/AP Series Power Supply
If commercial power is present at the site, and the power supply is currently powered
1.
by commercial AC line voltage, turn the battery breaker OFF on the power supply and
disconnect the power supply from utility power.
If not already installed, install the RPM card. Refer to the instructions that come with this
2.
assembly.
WARNING!
Installing the XP-EDH-A2 transponder at an Alpha AM power supply site requires shutting
down the power supply. If a short power interruption is not feasible, you must use an
alternate source of system power during the installation of the transponder. This is
necessary to install the RPM interface card, and to make connections to the output of the
power supply to permit monitoring of the output voltage of the power supply.
If a short power interruption is not feasible, you must use an alternate source of system
power during the installation of the transponder.
3.3.1 Connecting the XP-EDH-A2 to an AM/AP Series
Follow Fig. 3-9 to make connections between the transponder, the power supply site
and battery string.
NOTE:
The RPM card cannot be installed while the power supply is running on utility or battery power.