Page 19

background image

19

745-838-B2-001 Rev. A

3.0

Installation Instructions for Specifi c Power Supplies, continued

3.1

Alpha XM2 Series, continued

3.1.6 Provisioning the Network for the XM2 Series

The transponder must be recognized by the CMTS as a valid device, be able to
obtain an IP address and communicate with the SNMP management server.

Load the transponder’s MAC address into the CMTS.

1.

Compile the two MIBs using a network manager or MIB browser software.

2.

Setup SNMP using two proprietary MIBs fi les.

3.

Set the MIBS points for the XM2 as follows:

4.

For XM2
Oid: 1.3.6.1.4.1.2183.2.3.3.1.2 set to (2) (power supply
selection)
Oid: 1.3.6.1.4.1.2183.2.3.6.5 set to (4) (output voltage
scaling)
Oid: 1.3.6.1.4.1.2183.2.3.6.6 set to (1)for 110V powered
supply or (2) for 220V

Install and confi gure the DOCSIS confi guration fi le. See Section 2.1.9 for a

5.

sample fi le.

Refer to Section 4.0, "Proprietary Management Information Bases (MIBs)" for
detailed information.