beautypg.com

Activation – Alpha Technologies FlexPoint AX Series User Manual

Page 28

background image

28

010-318-C0-007, Rev. G

UPS Runtimes (minutes)

@

-40°F/-40°C

@

-4°F/-20°C

@ 77°F/25°C

LOAD (W)

4

820

1100

1200

7

360

560

800

10

160

360

500

15

80

195

320

18

156

240

UPS Runtimes (minutes)

@ -40°C/-40°F

@ -4°F/-20°C

@ 77°F/25°C

LOAD (W)

10

750

1080

1240

15

400

680

940

20

260

440

680

25

160

340

480

30

140

232

400

5.3

System Runtime and Battery Charging

The tables below show typical UPS runtimes in minutes as a function of temperature and load and

battery charging capacity retention ratio as a function of storage time and temperature.

5. Activation

Table 5-2, AX-12D-BBPS-7.2 UPS Runtimes as a function of Temperature and Load

Table 5-3, AX-12D-BBPS-17 UPS Runtimes as a function of Temperature and Load