2. Applications
NID/NIU/ONT
Cable through wall
AX18-12-HC
Indoor 120Vac
outlet
•
Indoors to Outdoors
•
Cable length under 100’
• UPS
required
Less than 10' of cable
(+/- and Alarms)
(See NOTE 2)
NOTE:
1. Use 14AWG (preferred) to 16AWG (minimum) for the cabling between the Home Converter/Power
Converter and battery housing. Use only cable rated for the outdoor environment. The maximum cable
length is determined by the maximum output voltage of the Power Converter/Home Converter minus the
voltage drop required by the Battery Module to properly charge the battery.
2. Use 18AWG (minimum) stranded cable for the +/- connections, and 18AWG to 22AWG cable for the
alarm connections between the battery housing and the NID/NIU/ONT. Use only cable rated for the
outdoor environment. The maximum cable length is calculated such that the minimum input voltage of the
ONT used in the confi guration is less than or equal to the lowest battery voltage (just above battery cutoff)
minus the voltage drop of the cable.
AX-12D-BBPS
Battery Housing
(shown)
Distance
Wire Size
0'–50'
#16 AWG
50'–100'
#14 AWG
11.6Vdc to 16Vdc
nominal output voltage
11.6-16 Vdc output
voltage
8' in length
Less than 10' of cable
(+/- and Alarms)
(See NOTE 3)
2.3
Outdoor UPS Confi guration
• Outdoors
•
Cable length under 100'
• UPS
required
2.4
Indoor to Outdoor UPS Confi guration
NID/NIU/ONT
AX-POWER-RING
and AX18-12D-PC
Assembly installed in
meter base
AX-12D-BBPS
Battery Housing
(shown)
Up to 100' of three wire (+, -, and control) cable
(See NOTE 2)
Up to 100' of three wire
(+, -, and control)
cable (See NOTE 1)