beautypg.com

Installation for submersible pump cutoff – Franklin Fueling Systems DC404-4 Controller User Manual

Page 4

background image

4

Installation for Submersible Pump Cutoff

Notice! Only qualified service technicians experienced

with petroleum dispensing and pumping systems

should install the DC400 system.

This controller is NOT for use with

3-phase pumps or Variable Frequency

Drive pump installations.

Notice! Do not exceed the 12 A (continuous), 250 VAC relay

contact rating of this controller. Relay contacts are not

fused. This controller is suitable for most submersible

pumps rated up to 2 hp @ 250 VAC and 1

½ hp @

120 VAC. provided the maximum pump motor

service factor amperage is 12A or less. Contact the

submersible pump manufacturer if in doubt.

Remove power to avoid possible

electrocution or ignition of explosive

gasoline vapors.

1. Shut off power to the STP. Lock out and tag the

corresponding STP circuit breaker.

2. In pump cutoff installations the 404-4 controller

will be connected directly to the integral electrical

junction box on the STP via rigid explosion proof

conduit. Since STP sump installations can vary,

the installer will need to determine where best to

place the controller in the sump and then procure

the necessary conduit and fittings.

A typical means of connecting the controller to

an STP via an explosion proof union is shown in

Figure 3. All fittings must be UL listed and suitable

for use in a Class I, Div 1, Group D environment.

If the STP junction box does not have a removable plug or

opening, installation adapters are available as listed below.

Installed STP

Installation Adapter

FE Petro

TS-FE

Red Jacket

TS-RJ

Red Jacket Quantum

TS-RJQ

404-4

Controller

To Sensor

Connection

Explosion Proof Union

STP Junction Box Cover

NOTE: Use reducer to connect ¾" conduit

to ½" cover opening.

EYS

Figure 3: Typical Connection to STP

Warning

Warning

6. Connect the sensor wire cable coming from the 404-4 controller to the appropriate Franklin Fueling Systems

sensor. Refer to the sensor’s installation instructions for installation, wiring and testing of the sensor.

The sensor must be installed in accordance with the sensor’s control drawing and with Franklin Fueling System’s control

drawing 000-1737.

7. Double check all dispenser & controller power wiring to be sure it is correct then replace the dispenser power

entry junction box cover. Secure the cover with all of the bolts previously retained.

8. Turn the dispenser power back on. The dispenser should operate normally.
9. Replace and secure lower dispenser door(s).

10. Test the DC400 dispenser cutoff by submerging the sensor in water. The dispenser should shut off and remain off

as long as the sensor is submerged.

ORG/BLK

ORG

BLK

WHT

Sensor

404-4 Controller

Dispenser Main Junction Box

12A, 240VAC

G

G

GRN/YEL

GRN

Dispenser

Breaker

Refer to MFG

wiring schematic

for terminal block /

wire connections

To Dispenser

Inputs

To Dispenser Earth Ground terminal

Figure 2: Power Wiring Schematic for Controller Dispenser Connection