2 sensor administration under modbus, Sensor administration under modbus -6 – YSI DIQ/S 182-MOD System 182 User Manual
Page 118
Modbus connection
System 182
7 - 6
ba76025e01
02/2012
Query and response
telegram
Data transmission takes place via query and response telegrams. The
form of the telegrams is determined by the Modbus RTU protocol. The
Modbus master transmits a query telegram with a Modbus command to
the Modbus slave (here, the DIQ/S 182-MOD). The Modbus slave
transmits a response telegram with the requested data from the sensor
data block or an error message.
Supported
Modbus commands
The DIQ/S 182-MOD provides the data block for read access only.
Writing Modbus commands are not carried out.
7.4.2
Sensor administration under Modbus
Preparation of the IQ S
ENSOR
N
ET
for communication with the Modbus
may require, e.g. the following:
Creating an IQ S
ENSOR
N
ET
system with specific assignment of
sensor numbers to sensors
Creating several IQ S
ENSOR
N
ET
systems with the identical
assignment of sensor numbers to sensors
Changing the order of the sensors in an already installed system
Creating the assignment
of sensor numbers
You want to install an IQ S
ENSOR
N
ET
system and, at the same time,
create a specific sequence of sensor number assignments to the
sensors.
Modbus commands
Command code
Read Input Register
04h
Read Discrete Inputs
02h
Read Holding Register
03h
Read Coils
01h
1
Carry out a system start without any sensors (see section
3.10).
2
Connect the sensors to the system in the required order. With
each sensor wait until the system has recognized the sensor.