2 aquaforce modbus communication points – Xylem 10 001 262R5 AquaForce Pump Controller User Manual
Page 58

AQUAFORCE Installation, Operation, and Maintenance
52
Appendix
7.2 AquaForce MODBUS Communication Points
Function Points # Point
Range/
Modbus Units
Code
Description
Value
Address
02
1
Pump #1 VFD Failure
1 = Failure
0 = O.K.
10001
02
2
Pump #1 Off Alarm
1 = Alarm
0 = O.K.
10002
02
3
Pump #2 VFD Failure
1 = Failure
0 = O.K.
10003
02
4
Pump #2 Off Alarm
1 = Alarm
0 = O.K.
10004
02
5
Pump #3 VFD Failure
1 = Failure
0 = O.K.
10005
02
6
Pump #3 Off Alarm
1 = Alarm
0 = O.K.
10006
02
7
Pump #4 VFD Failure
1 = Failure
0 = O.K.
10007
02
8
Pump #4 Off Alarm
1 = Alarm
0 = O.K.
10008
02
9
System Reset Required
1 = Yes
0 = No
10009
02
10
Pump #1 Enabled
1 = Enabled 0 = Disabled
10010
02
11
Pump #2 Enabled
1 = Enabled 0 = Disabled
10011
02
12
Pump #3 Enabled
1 = Enabled 0 = Disabled
10012
02
13
Pump #4 Enabled
1 = Enabled 0 = Disabled
10013
02
14
Pump #1 On/Off
1 = On
0 = Off
10014
02
15
Pump #2 On/Off
1 = On
0 = Off
10015
02
16
Pump #3 On/Off
1 = On
0 = Off
10016
02
17
Pump #4 On/Off
1 = On
0 = Off
10017
02
18
System Start/Stop
1 = Start
0 = Stop
10018
02
19
Analog Input #1 Failure
1 = Failure
0 = O.K.
10019
02
20
Analog Input #2 Failure
1 = Failure
0 = O.K.
10020
02
21
General Alarm
1 = Alarm
0 = O.K.
10021
02
22
System Operation Mode
1 = Auto
0 = Manual
10022
05
1
Pump Sequence Alternation
1 = Yes
0 = No
00001
05
2
System Reset Request
1 = Yes
0 = No
00002
05
3
System Start / Stop
1 = Start
0 = Stop
00003
04
1
Discharge Pressure
0 to Span (in AquaForce
30001
PSI
User Setup Menu)
04
2
Suction Pressure
0 to Span (in AquaForce
30002
PSI
User Setup Menu)
04, 06
3
AI #1
0 to Span (in AquaForce
30003,
User Setup Menu)
40003
04, 06
4
AI #2
0 to Span (in AquaForce
30004,
User Setup Menu)
40004
04, 06
5
Setpoint #1
0 to Span (in AquaForce
30005,
User Setup Menu)
40005
04
6
System Power (KW)
0 to Span (in AquaForce
30006
KW
User Setup Menu)
04
7
Drive #1 Current
0 to Span (in AquaForce
30007
A
User Setup Menu)
04
8
Drive #2 Current
0 to Span (in AquaForce
30008
A
User Setup Menu)
04
9
Drive #3 Current
0 to Span (in AquaForce
30009
A
User Setup Menu)