Xylem 10 001 262R5 AquaForce Pump Controller User Manual
Page 30

AQUAFORCE Installation, Operation, and Maintenance
24
Password Menu Items (continued)
Menu Item
Variable
Default Range Field
Value
Verify
VERIFY THE PASSWORD
PASSWD >_ _ _ _ _ _<
After entering data in password definition screen this
screen requires the user to confirm the requested
password. If the confirmed number does not agree with
the first number the Enter New Password screen is
repeated to allow the user to get both input screens
to agree.
4.10.13 I/O setup menu
Paths: Status Screens / Set up(3) / System(4) / IO Setup(9)
See the following table for all
I/O Setup menu items.
NOTE: The total available number of I/O to be configured depends on the system setup. Complete all previous
setup screens, specifically pumps and sensors prior to completing the following.
I/O Setup Menu Items
Menu Item
Variable
Default Range Field
Value
DO
Total Avail. DO = #
N/A
0-99
This screen can not be modified. It is here to advise the
user of how many digital outputs can be customized
* DO No: ####
N/A
0-999
Enter the output to be configured as it appears on the
terminal number.
* Code: ###
0
0-255
Enter the code to define the desired functionality of the
output. Valid codes are defined in the Appendix of this
manual.
AO
Total Avail. AO = #
N/A
0-99
This screen can not be modified. It is here to advise the
user of how many analog outputs can be customized
* Code: ###
0
0-255
Enter the code to define the desired functionality of the
output. Valid codes are defined in the Appendix of
this manual.
NOTE: If a programming error happens, an error message is displayed. An error may be due to reprogramming
an input that is currently used by the system or inputting an undefined code number.
4.10.14 Communication Menu
Paths: Status Screens / Set up(3) / System(4) / Communication(10)
The
MODBUS screen is displayed below:
Modbus
9600, 8, 1, 1, N RTU
Node: # Al Ovrd: $
OK: $(Y/N)
The first line confirms setup for Modbus protocol. The second line defines the 9600 bps baud rate, 1 stop bit, 1
start bits, and no parity. The third line requires user input. Obtain the node number from the manufacturer that
supplied the device that will communicate with the Controller.
Installation