AQUAFORCE Installation, Operation, and Maintenance
29
Installation
4.10.25 Analog input test
Paths: Status Screens / Set up(3) / Test(5) / AI(3)
The Analog Input Test screen is displayed below:
Analog Inputs
1=###%
2=###%
The signal received on the corresponding analog input channel will be indicated in percent next to each input.
4mA = 0%, and 20mA = 100%. Analog inputs 1-2 are 4-20mA inputs. Press
CLEAR key to exit the test.
4.10.26 Analog output test
Paths: Status Screens / Set up(3) / Test(5) / AO(4)
The Analog Output Test screen is displayed below:
Analog Output Test
AO1=###%
OK: $(Y/N)
The signal sent through the corresponding analog output channel will be indicated in percent next to each output.
4mA = 0%, and 20mA = 100%. Analog output is 4-20mA output. Press
CLEAR key to exit the test.
4.10.27 LED test
Paths: Status Screens / Set up(3) / Test(5) / LED(5)
The LED test screen is displayed below:
LED Test
*** SOLID ***
*** OFF ***
*** FLASHING ***
All of the LED’s on the keypad will turn on, off, and then flash. The current status will be displayed on the
screen. The LED test is self terminating.
4.10.28 Key test
Paths: Status Screens / Set up(3) / Test(5) / Key(6)
The
KEY test screen is displayed below:
Key Test
Press a key to test
Press clear to exit
Press any key except for the
CLEAR key, and the display will confirm that the key is working by displaying the
key name. Press
CLEAR key to exit.
4.10.29 Display test
Paths: Status Screens / Set up(3) / Test(5) / Display(7)
The
DISPLAY test screen is shown below:
Press Clear To Exit
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
The display will show all black characters. Press
CLEAR key to exit the test.