Data Sheet
KBVW006A0B Series Sixteenth-Brick Power Modules
36–75Vdc Input; 12.0Vdc Output; 6A Output Current
July 9, 2013
©2012 General Electric Company. All rights reserved.
Page 4
Feature Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Feature Descriptions for additional information.
Parameter
Device
Symbol
Min
Typ
Max
Unit
Remote On/Off Signal Interface
(V
IN
=V
IN, min
to V
IN, max
; open collector or equivalent,
Signal referenced to V
IN-
terminal)
Negative Logic: device code suffix “1”
Logic Low = module On, Logic High = module Off
Positive Logic: No device code suffix required
Logic Low = module Off, Logic High = module On
Logic Low - Remote On/Off Current
All
I
on/off
0.15 mA
Logic Low - On/Off Voltage
All
V
on/off
-0.7
0.6 V
dc
Logic High Voltage – (Typ = Open Collector)
All
V
on/off
2.4
15 V
dc
Logic High maximum leakage current
All
I
on/off
25
μA
Turn-On Delay
1
and Rise Times
(I
O
=I
O, max ,
V
IN
=V
IN, nom,
T
A
= 25
o
C)
Case 1: Input power is applied for at least 1 second
and then the On/Off input is set from OFF to ON (T
delay
= from
instant at which On/Off signal is ON until V
O
= 10% of V
O, set
).
All T
delay
— 20
— msec
Case 2: On/Off input is set to Logic Low (Module
ON) and then input power is applied (T
delay
from
instant at which V
IN
= V
IN, min
until V
o
=10% of V
O,set
)
All T
delay
— — 150 msec
Output voltage Rise time (time for V
o
to rise from 10%
of V
o,set
to 90% of V
o, set
)
All T
rise
— 5 12 msec
Output voltage overshoot – Startup
All
— 3
%
V
O, set
I
O
= I
O, max
; V
IN
=V
IN, min
to V
IN, max
, T
A
= 25
o
C
Prebiased Output Load Performance:
All Monotonic
Output Start up characteristic
Back Bias current drawn from output (Module Enabled)
All
-50
mA
dc
Back Bias current drawn from output (Module Disabled)
All
-50
mA
dc
Remote Sense Range
All
V
SENSE
10 %
V
O, set
Output Voltage Adjustment Range
All
80
110
% V
O, set
Output Overvoltage Protection
All V
O, limit
13.8
16.5 V
dc
Overtemperature Protection – Hiccup Auto Restart
All
T
ref
135
O
C
Input Undervoltage Lockout
All
V
UVLO
Turn-on Threshold
32 34.5 V
dc
Turn-off Threshold
27.5 30
V
dc
Hysteresis
1 2
V
dc
1.
The module has an adaptable extended Turn-On Delay interval, T
delay
, of 25mS. The extended T
delay
will occur when the module restarts following either: 1)
the rapid cycling of Vin from normal levels to less than the Input Undervoltage Lockout (which causes module shutdown), and then back to normal; or 2)
toggling the on/off signal from on to off and back to on without removing the input voltage. The normal Turn-On Delay interval, T
delay
, will occur whenever a
module restarts with input voltage removed from the module for the preceding 1 second.
2.
The module requires a minimum of 220
μF external output capacitor to prevent shutdown during no load to full load transients and to avoid exceeding the
OVP maximum limits during startup into open loop fault conditions.