3 function explanation – GE Industrial Solutions AF-300 G11 User Manual
Page 60
5-7
Data subject to change without notice 7/07. © 2007 GE Drives
F00 Data protection
F 0 0
D A T A
P R T C
Set value
0 : data can be changed
1 : data cannot be changed
This function protects the system by blocking any data
changes from the keypad panel.
Setting procedure:
0 to 1:
Press the
STOP
and
keys simultaneously to
change the value from 0 to 1, then press
the
FUNC
DATA
to validate the change.
1 to 0:
Press the
STOP
and
keys simultaneously
to change the value from 1 to 0, then press
the
FUNC
DATA
key to validate the change.
F01 Frequency setting 1
F 0 1
F R E Q
C M D 1
This function determines the method to be used for setting
frequency.
NOTE: Use only one terminal - V2 or C1, exclusively.
0:
Keypad operation (
or
key)
1:
Voltage input (terminal 12 and V2) (0 to +10 VDC,
0 to +5VDC)
2:
Current input (terminal C1) (4 to 20 mA DC)
3:
Voltage and current input (terminals 12 and C1)
4:
Reversible operation with polarity (terminal 12)
(0 to
±
10 VDC)
Reversible operation with polarity (terminal 12 and V1
option) (0 to
±
10 VDC)
Related functions E01 to E09 (Set values 21
6:
Inverse mode operation (terminal 12 and V2)
(+10 to 0 VDC)
7:
Inverse mode operation ( terminal C1)(20 to 4 mA DC)
8:
UP/DOWN control 1 (initial freq. = 0 Hz
9:
UP/DOWN control 2 (initial freq. = last value)
Related functions E01 to E09 (Set values 17, 18)
10. PATTERN operation
Related functions: C21 to C28
11: DI option or Pulse train input
For details, see instruction manual on options.
F02 Operation method
F 0 2
O P R
M E T H O D
This function determines the input method for operation
commands.
0:
Keypad operation (
FWD
or
REV
or
STOP
key)
1:
Terminal operation (
STOP
key active)
2:
Terminal operation (
STOP
key inactive)
3:
Terminal operation (
STOP
key active) with GE start
software
4:
Terminal operation (
STOP
key inactive) with GE start
software
This function can only be changed when terminals
FWD
and
REV
are open.
REMOTE/LOCAL switching from the keypad panel
automatically changes the set value from 0 to 3 of this
function.
5.3 Function Explanation
F: Fundamental function